Introduction

This manual provides essential information for the safe and efficient operation of your Delta MS300 Series Frequency Converter. Please read this manual thoroughly before installation, operation, or maintenance to ensure proper usage and to prevent damage to the unit or associated equipment.

The Delta MS300 series is a standard compact vector control drive that inherits Delta’s superior drive technology. It supports both IM and PM motor control, offering high efficiency and flexibility. It is designed for various general-purpose applications.

Видео: Бүттүview of Delta MS300 and ME300 Series Frequency Converters, showcasing different models and internal components.

Коопсуздук маалыматы

WARNING: Read the user manual before operation. Risk of electrical shock. Wait 10 minutes after removing power before servicing. Do not connect AC power to output terminals U/T1, V/T2 and W/T3.

Always ensure the power is off and wait for the specified discharge time before performing any maintenance or inspection. Improper handling can lead to severe injury or death.

Орнотуу жана орнотуу

Алгачкы текшерүү

AC кыймылдаткычын алгандан кийин, төмөнкүлөрдү текшериңиз:

  1. Inspect the unit after unpacking to ensure it was not damaged during shipment.
  2. Негизги т.бtage is within the range as indicated on the nameplate.
  3. Before applying the power, please make sure that all devices, including mains power, motor, control board and digital keypad, are connected correctly.
  4. When wiring the AC motor drive, please make sure that the wiring of input terminals "R/L1, S/L2, T/L3" and output terminals "U/T1, V/T2, W/T3" are correct to prevent damage to the drive.
  5. When power is applied, select the language and set parameters via the digital keypad (KPMS-LE01).
  6. When executing a trial run, please begin with a low speed and then gradually increase the speed until the desired speed is reached.

Фамилия маалыматы

The product nameplate provides critical information about your specific unit. Refer to the diagram below for details.

Delta MS300 Inverter Nameplate Diagram

Diagram: Delta MS300 Inverter Nameplate Layout and Information.

  • Модел: VFD 4A8MS23ANSAA (Exampле)
  • Киргизүү: Normal Duty: 3PH 200-240V 50/60Hz 6.0A, Heavy Duty: 3PH 200-240V 50/60Hz 5.8A
  • Чыгуу: Normal Duty: 3PH 0-230V 5A 1.9KVA 1HP, Heavy Duty: 3PH 0-230V 4.8A 1.8KVA 1HP
  • Жыштык диапазону: 0-599 Гц
  • Орнотулган программанын версиясы: 1.00
  • Корпусунун түрү: (IPXX)
  • Сертификаттар: (UL, CE, etc.)
  • Сериялык номери: (Unique identifier)

Serial Number Structure

Understand the serial number to identify production details of your unit.

Delta MS300 Serial Number Explanation

Diagram: Breakdown of the Delta MS300 serial number components.

Model Name Interpretation

The model name provides detailed specifications about the drive.

Delta MS300 Model Name Structure

Diagram: Explanation of the Delta MS300 model naming convention.

  • VFD: Variable Frequency Drive
  • Номиналдуу чыгаруу ток: e.g., 4A8 for 4.8A
  • Сериялар: MS (MS300 Standard Micro Drive)
  • Киргизүү көлөмүtage: 11 (115V 1-phase), 21 (230V 1-phase), 23 (230V 3-phase), 43 (460V 3-phase)
  • Коргоо деңгээли: A (IP20), E (IP40), M (IP66)
  • EMC Function: N (No function), F (Internal Filter)
  • Коопсуздук функциясы: S (Built-in STO)
  • Орнотуу түрү: A (Standard)
  • Version Type: A (Standard)

RFI Jumper Configuration

The RFI (Radio Frequency Interference) jumper is crucial for EMC performance and surge protection.

  • Varistors/MOVs are connected phase to phase and phase to ground to protect against surges.
  • Removing the RFI jumper disconnects internal capacitors from ground, which can damage circuits and increase ground leakage current.
  • If the drive has a built-in EMC filter, the RFI jumper connects filter capacitors to ground. Removing it can reduce the effectiveness of the filter.
  • For single drives with built-in EMC filters, removing the RFI jumper may trigger a Residual Current Device (RCD).

To remove the RFI Jumper:

RFI Jumper Removal Instructions

Diagram: Visual guide for locating and removing the RFI jumper for Frame A-F and Frame B-F models.

  1. Loosen the screw and remove the RFI Jumper (as shown in the diagram).
  2. Fasten the screw again after the RFI Jumper is removed.
  3. For Frame B-F models (with built-in EMC filter), remove the RFI Jumper with a screwdriver.

Бурама момент: 4-6 kg-cm / [3.5-5.2 lb-in.] / [0.39-0.59 Nm]

Жерге салуу боюнча нускамалар

Proper grounding is essential for safety and EMC compliance.

  • Ensure the drive is properly grounded during installation.
  • Cable diameters must comply with local safety regulations.
  • Shielded cables must be connected to the ground of the drive.
  • Shield of shielded power cables can only be used as the ground for equipment when the aforementioned points are met.
  • When installing multiple drives, do not connect them in series; connect each drive to ground individually.

Important points regarding ground connection:

Grounding Diagrams for Asymmetric Ground Systems

Diagram: Examples of correct and incorrect grounding setups for various AC systems.

Floating Ground System (IT Systems):

In an IT system (ungrounded system or high impedance/resistance), observe the following:

  • Disconnect the RFI Jumper.
  • Check for excess electromagnetic radiation affecting nearby low-voltagэлектрондук схемалар.
  • If necessary, install an extra electrostatic shielded cable on the power supply side between the main circuit and the control terminals to increase security.
  • Do not install an external EMC filter. The EMC filter is connected to ground through the filter capacitors, which can damage the drive in an IT system.

DC Reactor Installation

A DC reactor can improve power factor, reduce input current, and reduce interference. It stabilizes the DC-bus voltage. For 115V models, no DC choke is needed.

DC Reactor Wiring Diagram

Diagram: Wiring connections for an optional DC reactor and brake resistor.

The DC reactor is installed between terminals +1 and +2. The jumper shown in the diagram needs to be removed before installation.

Эскертүү:

  • It is recommended to install a protective circuit breaker to protect the system from damage.
  • When a fault occurs, use the circuit breaker to shut off power.
  • RB and RC are multi-function relay contacts.

Иштөө нускамалары

The Delta MS300 series features a user-friendly digital keypad for control and parameter settings. The main control buttons include RUN, STOP/RESET, MODE, and ENTER, along with arrow keys for navigation and a potentiometer for speed adjustment.

Delta MS300 Control Panel

Image: Front panel of the Delta MS300 frequency converter showing control buttons and display.

For detailed parameter settings and advanced operation modes, please refer to the comprehensive user manual available from Delta Electronics.

Техникалык тейлөө

Regular maintenance ensures the longevity and optimal performance of your Delta MS300 frequency converter.

  • Тазалоо: Keep the unit clean and free from dust and debris. Use a soft, dry cloth for cleaning. Do not use liquid cleaners or solvents.
  • Вентиляция: Ensure proper airflow around the unit. Regularly check that ventilation openings are not obstructed.
  • Байланыштары: Periodically check all wiring connections for tightness and signs of corrosion. Loose connections can lead to overheating or malfunction.
  • Экологиялык шарттар: Operate the drive within its specified environmental conditions (temperature, humidity, altitude) to prevent premature failure.
  • Текшерүү: Visually inspect the unit for any signs of damage, discoloration, or unusual odors. If any issues are detected, power off the unit immediately and consult a qualified technician.

WARNING: Always disconnect power and wait at least 10 minutes for capacitors to discharge before performing any maintenance or inspection.

Проблемаларды чечүү

This section provides general guidance for common issues. For detailed error codes and advanced troubleshooting, refer to the full Delta MS300 user manual.

Жалпы маселелер жана чечимдер:

  • Drive does not power on:
    • Негизги электр менен жабдууну жана өчүргүчтү текшериңиз.
    • Бардык кубат туташуулары коопсуз экенин текшериңиз.
    • Киргизүү көлөмүн камсыз кылыңызtage matches the nameplate specifications.
  • Мотор иштебейт:
    • Check motor wiring for correct connections (U/T1, V/T2, W/T3).
    • Verify control signals (RUN command) are active.
    • Check for any error codes displayed on the keypad.
    • Ensure parameters are set correctly for the motor and application.
  • Over-current or Over-voltage күнөө:
    • Check for sudden load changes or mechanical issues with the motor/load.
    • Verify acceleration/deceleration times are appropriate for the application.
    • Киргизүүнү камсыз кылуу томtage is stable and within limits.
    • Consider installing a DC reactor if surge voltage is an issue (refer to DC Reactor Installation section).
  • RFI/EMI interference:
    • Көрсөтмөлөргө ылайык туура жерге туташтырууну камсыз кылуу.
    • Use shielded motor cables and ensure shields are properly grounded.
    • Verify RFI jumper is correctly installed or removed based on system requirements.

Техникалык шарттар

The Delta MS300 series frequency converters are available in various power ratings and configurations. Below are general specifications and dimensions.

Продукттун жалпы мүнөздөмөлөрү

АтрибутНарк
Бренд атыSvit SensoPlan by Trumsense (Delta)
Модель номериDelta MS300 Series Converter
Чыгуу күчү1 - 200 KW (various models)
TypeDC/AC Inverters
СалмагыApprox. 2 kg (varies by model)
OriginМатерик Кытай
СертификацияNone (as listed, typically UL, CE, etc. are present on product)

DC Reactor Dimensions and Specifications

DC Reactor Dimensions and Specifications Table

Diagram and Table: Dimensions and electrical specifications for various DC reactor models.

Motor Cable Length Guidelines

The length of the motor cable can affect performance and measurements. Longer cables can increase leakage current and surge voltage.

Motor Cable Length Guidelines Table

Table: Recommended maximum shielded and non-shielded cable lengths for different VFD models, compliant with IEC 60034-17.

To prevent issues with long motor cables:

  • Жакшыртылган изоляциясы бар мотор колдонуңуз.
  • Connect an output reactor (optional) to the output terminals of the AC motor drive.
  • Reduce the motor cable length to the values provided in the table.

Product Dimensions (by Frame Size)

Dimensions vary by the drive's frame size. Refer to the diagrams below for specific measurements (Unit: mm [inch]).

Frame A Dimensions Diagram

Diagram: Dimensions for Frame A models (e.g., VFD1A6MS11ANSAA).

Frame B Dimensions Diagram

Diagram: Dimensions for Frame B models (e.g., VFD7A5MS23ANSAA).

Frame C Dimensions Diagram

Diagram: Dimensions for Frame C models (e.g., VFD4A8MS11ENSAA).

Frame D Dimensions Diagram

Diagram: Dimensions for Frame D models (e.g., VFD25AMS23ANSAA).

Frame E Dimensions Diagram

Diagram: Dimensions for Frame E models (e.g., VFD33AMS23ANSAA).

Колдонуучу сунуштар

  • Always double-check wiring before applying power to avoid damage.
  • Start with low speeds during initial setup and gradually increase to desired operating speed.
  • Refer to the detailed model name and serial number information to ensure you have the correct unit and specifications for your application.

Кепилдик жана колдоо

This Delta MS300 series frequency converter is manufactured to high-quality standards. For specific warranty terms and conditions, please refer to the official Delta Electronics warranty policy or contact your authorized distributor.

For technical support, service, or further inquiries, please contact Delta Electronics customer service or your local support center. Ensure you have your product model and serial number ready when seeking support.

Official documentation and software updates may be available on the Delta Electronics webсайт.


Delta MS300 & ME300 сериясы өзгөрүлмө жыштыктагы дисктер (VFDs)view

Delta MS300 & ME300 сериясы өзгөрүлмө жыштыктагы дисктер (VFDs)view

0:47 • 1280×720 • visual_overview

Тектеш документтер - MS300 сериясы

Preview Delta Standard Compact Drive MS300 Series User Manual
User manual for Delta Standard Compact Drive MS300 Series, detailing installation, specifications, wiring, optional accessories, and operational guidance for industrial automation applications.
Preview Delta VFD Factory Reset Guide
Step-by-step instructions for performing a factory reset on Delta VFD drives, including navigating menus and setting parameters for different frequencies.
Preview Delta MS300 Variable Frequency Drive Datasheet
Comprehensive datasheet for the Delta MS300 series of Variable Frequency Drives (VFDs), detailing specifications, type number key, dimensions, wiring diagrams, and programming parameters.
Preview Delta VFD-M Series User Manual: High Performance AC Motor Drives
Comprehensive user manual for the Delta VFD-M Series AC Motor Drives. Covers installation, parameter settings, troubleshooting, maintenance, and specifications for high-performance, low-noise micro-type AC motor control.
Preview DELTA VFD-EL Series Sensorless Vector Control Micro Drive User Manual
Comprehensive user manual for the DELTA VFD-EL Series Sensorless Vector Control Micro Drive, covering installation, wiring, parameter settings, operation, and troubleshooting for industrial automation applications.
Preview Delta MS300 Series Compact Drive User Manual
This comprehensive user manual provides detailed information on Delta's MS300 Series Standard Compact Drives, essential for digitized automation. It covers installation, specifications, wiring, operation, safety precautions, and optional accessories for industrial applications.