ACREL ACR10R-D36TE4

Acrel ACR10R KWh 3 Phase Energy Meter Instruction Manual

Model: ACR10R-D36TE4 | Brand: ACREL

1. Киришүү

The Acrel ACR10R KWh 3 Phase Energy Meter is designed for bidirectional energy monitoring, particularly suitable for solar power applications. It accurately measures active and reactive power, current, voltage, frequency, and power factor in three-phase systems. This meter supports communication via RS485 (MODBUS-RTU) and can be paired with external split-core current transformers (CTs) or Rogowski coils for flexible installation. Its compact design allows for 35mm DIN rail mounting, making it ideal for energy-saving renovation projects and power monitoring in distributed photovoltaic grid-connected systems.

Acrel ACR10R Energy Meter with three split-core current transformers
Figure 1: Acrel ACR10R Energy Meter with three split-core current transformers.

2. Продукциянын өзгөчөлүктөрү

  • Өлчөө мүмкүнчүлүктөрү: Measures 3-phase active power, reactive power, current, voltagд, жыштык жана кубаттуулук фактору.
  • Current Rating Options: Supports various current ratings up to 300A with external split-core CTs (10mm/80A, 16mm/120A, 24mm/200A, 36mm/300A) or up to 20000A with Rogowski coils.
  • Байланыш: RS485 interface with MODBUS-RTU protocol for data exchange.
  • Колдонмо: Ideal for distributed solar PV systems and anti-reflux inverter applications.
  • Дисплей: Clear LCD for parameter display and programming.
  • Орнотуу: Designed for easy 35mm DIN rail mounting.
  • Электр камсыздоо: Wide range AC (85~265V) or DC (100~350V) power supply.
  • Тастыктоо: CE күбөлөндүрүлгөн.
  • Кошумча функция: Harmonic Monitoring.
  • Bidirectional Metering: Supports both active and reactive energy metering.
  • Keypad HMI: Integrated keypads for parameter display setting and communication configuration.
Key features of the ACR10R energy meter
Figure 2: ашыкview of ACR10R Energy Meter features.

3. Техникалык шарттар

КатегорияПараметрТолук маалымат
ГенералМодель номериACR10R-D36TE4
Өлчөмдөр85*64*54мм
ӨлчөөNet Work3-фаза 3-зым, 3-фаза 4-зым
Жыштык45~65Гц
Rated VoltageAC 57.7V/100V (100V), 220V/380V (400V)
Максималдуу иштөө агымы150A & Above (up to 300A with CTs, 20000A with Rogowski Coil)
Measuring Energy Range0-99999.9кВт/саат
Өлчөө параметрлериU, I, P, Q, S, PF, F (Voltage, Current, Active Power, Reactive Power, Apparent Power, Power Factor, Frequency)
ТактыкТактык классы1
Frequency тактыгы0.05Hz
КүчЭлектр камсыздооAC 85~265V or DC 100~350V; DC 24V(±10%); DC 48V(±10%)
Керектөө10VA
Батарея камтылганОоба
БайланышИнтерфейсRS485
ПротоколMODBUS-RTU
ДисплейTypeLCD
Дисплей режимиField LCD
Курчап турган чөйрөИштөө температурасы-10℃~55℃
Сактоо температурасы-20℃~70℃
Салыштырмалуу нымдуулук5%~95% (конденсация жок)
КоопсуздукКубат-жыштык туруштук берүү томtageAC2kV/1min (Auxiliary power, switch volume output, current input, voltage input, communication, pulse output, switch volume input)
Изоляцияга каршылык>100MΩ (Input, Output terminal to housing)
Dimensional drawing of the Acrel ACR10R energy meter
Figure 3: Dimensional drawing of the ACR10R Energy Meter.

4. Пакеттин мазмуну

The standard package for the ACR10R Energy Meter includes:

  • 1 x Acrel ACR10R 3 Phase Energy Meter
  • 3 x External Split-Core Current Transformers (CTs) - Specific current rating depends on the selected model (e.g., 80A, 120A, 200A, 300A)
  • Колдонуучунун Колдонмосу (бул документ)
Acrel ACR10R Energy Meter and three split-core current transformers
Figure 4: Contents of the ACR10R package.

5. Орнотуу жана орнотуу

5.1. DIN Rail Installation

  1. Push off the buckle on the back side of the meter.
  2. Install the meter onto a 35mm DIN rail by aligning the slot behind the meter with the rail.
  3. Buckle up the meter to fix it securely on the DIN rail.
  4. Ensure the meter is successfully installed and stable.
Steps for DIN rail installation of the energy meter
Figure 5: DIN Rail Installation Steps.

5.2. Current Transformer (CT) Installation

The ACR10R meter can be paired with either split-core CTs or Rogowski coils. Ensure correct polarity and secure connection for accurate measurements.

  • Split Core CT Installation: Open the CT, place the conductor through the center, and close it securely. Ensure the direction of current flow matches the CT's arrow for correct measurement.
  • Rogowski Coil Installation: Wrap the Rogowski coil around the conductor.
External CT dimensions and installation of split core CT and Rogowski coil
Figure 6: External CT dimensions and installation methods.

Video 1: Demonstration of energy meter and Rogowski coils.

6. Электр схемасы

Proper wiring is critical for the safe and accurate operation of the ACR10R energy meter. Refer to the following diagrams for common configurations.

6.1. General System Connection

Diagram showing solar panel, inverter, reflux monitoring meter, and grid connection
Figure 7: General system diagram for solar PV monitoring.

6.2. Detailed Wiring for 3-Phase Systems

Detailed wiring diagram for 3-phase, 4-wire 3CT, 3PT, 2CT, accessory power, and RS485 communication
Figure 8: Detailed wiring diagram for various 3-phase configurations, accessory power, and RS485 communication. Note: For CT secondary side short connection, ensure proper terminal connection. The fuse in the wiring diagram is recommended 0.5A or 3A. When the instrument is installed on site, it must correspond to the supporting open and closed transformer or Rogowski coil one by one, otherwise the measurement accuracy will be affected, and the connection between the two must be reliable.

6.3. Bidirectional Metering Diagram

Diagram illustrating bidirectional metering (power consumption vs. redundant power generation)
Figure 9: Bidirectional metering concept showing power consumption and redundant power generation.

6.4. Distributed Solar PV Application Diagram

Diagram of a house with solar panels and energy meter setup
10-сүрөт: Мисample of ACR10R integration in a distributed solar PV system.

7. Иштөө нускамалары

The ACR10R meter features an LCD display and keypad HMI for user interaction.

7.1. LCD дисплей

The LCD provides real-time readings of various electrical parameters such as voltage, current, power, frequency, and energy consumption. It also serves as the interface for programming and configuration.

Close-up of the LCD display on the energy meter
Figure 11: LCD Display for parameter viewing.

7.2. Keypad HMI

Use the integrated keypads (FN, Set, and arrow buttons) to navigate through menus, view different parameters, and configure settings such as communication parameters (address, baud rate) and wiring modes (3P3W, 3P4W).

Close-up of the keypad HMI for programming
Figure 12: Keypad HMI for navigation and programming.

8. Техникалык тейлөө

  • Тазалоо: Keep the meter clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Экологиялык шарттар: Зыяндын алдын алуу үчүн иштөө чөйрөсүнүн көрсөтүлгөн температура жана нымдуулук диапазондоруна туура келгенин текшериңиз.
  • Туташуу текшерүүлөрү: Мезгил-мезгили менен бардык зымдарды байланыштарды текшерип, алар бекем жана коррозияга учурабайт.
  • Программалык камсыздоонун жаңыртуулары: Өндүрүүчүнү текшериңиз webоптималдуу иштешин жана жаңы функцияларга жетүүнү камсыз кылуу үчүн бардык жеткиликтүү микропрограммаларды жаңыртуу үчүн сайт.

9. Кыйынчылыктарды

  • Дисплей/кубат жок: Check the power supply connections (AC 85~265V or DC 100~350V) and ensure they are within the specified range. Verify that the power source is active.
  • Туура эмес окуулар: Double-check all CT and voltage wiring connections for correct polarity and phase sequence. Ensure the CTs are correctly installed around the conductors. Verify the meter's configuration settings match your system.
  • Communication Issues (RS485): Confirm the RS485 wiring is correct (A to A, B to B). Check the communication parameters (baud rate, address) on the meter and the connected device (e.g., inverter, gateway). Ensure termination resistors are correctly used if necessary.
  • Эсептегич жооп бербейт: If the meter becomes unresponsive, try power cycling it (turn off, wait a few seconds, then turn on). If the issue persists, consult the warranty and support section.

10. Колдонуучунун кеңештери

  • Маалыматтарды каттоо: For applications requiring detailed historical data, such as measurement profiles every 15 minutes, ensure the optional data logging feature is enabled and configured. Refer to the programming interface for setup.
  • CT Selection: Always choose CTs with a current rating appropriate for your application to ensure accuracy and prevent damage.
  • Anti-Reflux Function: When using the meter with an inverter for anti-reflux, ensure the RS485 communication is correctly established and configured according to both the meter and inverter manuals.

11. Кепилдик жана колдоо

The Acrel ACR10R Energy Meter comes with a 2 жылдык кепилдик сатып алынган күндөн тартып. Бул кепилдик нормалдуу колдонуудагы материалдардагы жана жасалгадагы кемчиликтерди камтыйт.

For technical support, troubleshooting assistance, or warranty claims, please contact the ACREL Official Store or your authorized dealer. Provide your product model number (ACR10R-D36TE4) and a detailed description of the issue when seeking support.

CE Certification document for ACR series multi-functional power meters
Figure 13: CE Certification for ACR series multi-functional power meters.

Тектеш документтер - ACR10R-D36TE4

Preview Acrel D317 Rail-type Multifunction Electrical Instrument with External Split Core Current Transformer: Use and Installation Manual
Comprehensive use and installation manual for the Acrel D317 Rail-type Multifunction Electrical Instrument, featuring an external split-core current transformer. Details technical specifications, product functions, installation procedures, and communication protocols for industrial energy monitoring applications.
Preview Acrel ACR10R Rail-type Multifunction Electrical Instrument with External Split Core Current Transformer - Use and Installation Manual
This manual provides comprehensive instructions for the Acrel ACR10R series rail-type multifunction electrical instrument, including its specifications, functions, installation, programming, and RS485 MODBUS-RTU communication. It details technical parameters, connection modes, operation procedures, and troubleshooting guidance for industrial and commercial power monitoring applications.
Preview ADL100-ET Single-Phase Electric Meter Installation and Operation Instruction Manual
Comprehensive installation and operation guide for the Acrel ADL100-ET single-phase electric meter. This manual details technical specifications, functional descriptions, wiring instructions, display menus, programming procedures, and communication protocols (Modbus RTU).
Preview Acrel D318 Harmonic Meter Operation Instruction Manual
Operation instruction manual for the Acrel D318 External Roche Coil and Switched Transformer Harmonic Meter. Details features, technical specifications, and connection methods for energy saving and power monitoring applications.
Preview Acrel ADL3000-E Smart Meter: Installation and Operation Manual
Comprehensive installation and operation instructions for the Acrel ADL3000-E smart meter, covering technical specifications, wiring, display functions, and communication protocols.
Preview DJSF1352-RN Rail-Mounted DC Power Meter Installation and Operation Manual
This document provides comprehensive installation and operation instructions for the Acrel DJSF1352-RN rail-mounted DC power meter. It covers product specifications, technical parameters, wiring diagrams, operational guidance, menu settings, and communication protocols (Modbus-RTU, DLT645-07).