1. Продукт бүтүп калдыview
This manual provides detailed instructions for the Schneider LC1D series three-pole AC contactors. It covers quick start procedures, product specifications, nameplate details, type designation keys, rated specifications, and structural diagrams.
1.1 Тез баштоо
Before using the Variable Frequency Drive (VFD), perform the following checks:
- Пакеттен чыгаруу инспекциясы: Verify the package for damage or humidification. Ensure the drive type matches the label and all accessories (manual, keypad) are present.
- Колдонмону ырастоо: Check load type for VFD overload, motor current against VFD rated current, control accuracy, and incoming supply voltage correspondence.
- Курчап турган чөйрө: Ensure ambient temperature is between -10°C and 40°C (derate 1% for every additional 1°C above 40°C, max 50°C). Altitude should be below 1000m (derate 1% for every additional 100m above 1000m). Humidity should be below 90% with no condensation. Avoid direct sunlight, foreign objects, conductive dust, or flammable gas.
1.2 Продукттун спецификациялары
The LC1D series AC contactors are designed for various industrial control applications. Key specifications include:
| Функция | Спецификация |
|---|---|
| Киргизүү көлөмүtage (V) | Single-phase 220(-15%) – 240(+10%) Three-phase 220(-15%) – 240(+10%) Three-phase 380(-15%) – 440(+10%) |
| Киргизүү агымы (A) | Refer to 2.5 (Rated specifications) |
| Киргизүү жыштыгы (Гц) | 50Hz or 60Hz (Allowed range: 47-63Hz) |
| Output Voltage (V) | =the input voltage (error<5%) |
| Чыгуу ток (A) | Refer to 2.5 (Rated specifications) |
| Чыгуу күчү (кВт) | Refer to 2.5 (Rated specifications) |
| Чыгуу жыштыгы (Гц) | 50Hz/60Hz, fluctuation:±5% |
| Башкаруу режими | SVPWM |
| Максималдуу чыгаруу жыштыгы | 400Hz |
| Adjustable-speed ratio | 1:100 |
| Ашыкча жүктөө мүмкүнчүлүгү | 150% of rated current: 1 minute 180% of rated current: 10 seconds 200% of rated current: 1 second |
| Mountable method | Дубалга орнотулган |
| Булгануу даражасы | 2 |
| Тормоздоо бирдиги | Камтылган |
| DC реактору | Кошумча эмес |
| Тормоздук каршылык | Optional and external |
| EMC чыпкасы | Optional C3 or C2 filter |
1.3 Nameplate and Type Designation Key
The nameplate provides essential information about your VFD. An example nameplate for a 280 series VFD (e.g., 280-G2.2KW-B3-B) includes Model, Power (Output), Input, Output, and Serial Number. The CE, TUV, or IP rating is labeled according to product certification.
The type designation key helps identify specific features:
| Идентификатор | Аныктама | Толук сүрөттөмө |
|---|---|---|
| 1 | Product abbreviation | 280 серия |
| 2 | Power range + Load type | 2R2-2.2kW, G-Constant torque load |
| 3 | Тtage degree | 4: 380(-15%) - 440(+10%) 2: 220(-15%) - 240(+10%) S2: 220(-15%) - 240(+10%) |
| 4 | Лот № | B: standard braking unit |
1.4 Түзүмдүн диаграммасы
The following image illustrates the product structure, using LC1D09 as an example, highlighting key components and connection points.

А жарылды view further details the internal components:

үстү view of the contactor terminals:

Көрүү үчүнview of the product and its variants, please watch the following video:
2. Коопсуздук чаралары
Read this manual carefully and follow all safety precautions before moving, installing, operating, and servicing the VFD. Ignoring these precautions may result in physical injury, death, or device damage. The manufacturer is not responsible for damages incurred due to non-compliance.
2.1 Safety Definitions and Warning Signs
Understanding the terminology and warning signs is crucial for safe operation:
- Коркунуч: Indicates a hazardous situation which, if not avoided, will result in serious physical injury or death.
- Эскертүү: Indicates a hazardous situation which, if not avoided, could result in physical injury or damage to the devices.
- Эскертүү: Provides important information that, if not followed, could result in physical hurt.
- Квалификациялуу электриктер: Individuals who have professional electrical and safety training, are certified, and are familiar with all steps and requirements for installing, commissioning, operating, and maintaining the device.
| Кол коюу | аты | Instruction |
|---|---|---|
| ⚠ | коркунуч | Serious physical injury or even death may occur if related requirements are not followed. |
| ⚠ | Эскертүү | Тиешелүү талаптар аткарылбаса, физикалык жаракат же аппараттар бузулушу мүмкүн. |
| ⚡ | Электростатикалык разряд | Damage to the PCBA board may occur if related requirements are not followed. Do not touch. |
| ⚠ | Hot sides | Аппараттын капталдары ысып кетиши мүмкүн. Тийбе. |
| Эскертүү | Эскертүү | Physical hurt may occur if related requirements are not followed. |
2.2 Жалпы коопсуздук эрежелери
- Only qualified electricians are allowed to operate on the VFD.
- Always disconnect all power supplies and wait for the designated time (or until DC bus voltage is below 36V) before wiring, inspection, or changing components.
- Do not modify the VFD without authorization to prevent fire, electric shock, or injury.
- The radiator base may become hot during running; avoid touching it.
- Take precautions against electrostatic discharge when handling electrical parts.
- Install the VFD on fire-retardant material and keep it away from combustible materials.
- Connect braking optional parts according to the wiring diagram.
- Do not operate the VFD if it is damaged or has missing components.
- Avoid touching the VFD with wet items or body to prevent electric shock.
- Use appropriate moving and installing tools to ensure safe operation and prevent injury.
- Avoid physical shock or vibration during delivery and installation. Do not carry the VFD by its cover.
- Install away from children and public places.
- The VFD may not meet low voltage protection requirements above 2000m altitude.
- The pick-up current may exceed 3.5mA; ensure proper grounding with resistance less than 10Ω.
- Connect input (R, S, T) and motor (U, V, W) terminals correctly to prevent damage.
2.3 Commissioning and Running Safety
- Disconnect all power supplies before terminal wiring and wait for the designated time.
- Жогорку тtage is present inside the VFD during running; only perform keypad settings.
- The VFD may start automatically if P01.21=1; keep clear of the VFD and motor.
- The VFD is not an 'Emergency-stop device' and cannot be used for sudden motor braking. A mechanical braking device should be provided.
- Do not frequently switch the input power supply.
- For VFDs stored long-term, check and fix capacitance, then run again (refer to Maintenance and Hardware Fault Diagnose).
- Cover the front board before running to prevent electric shock.
2.4 Maintenance and Component Replacement Safety
- Only qualified electricians are allowed to perform maintenance.
- Disconnect all power supplies and wait for the designated time before working on terminals.
- Prevent screws, cables, or other conductive materials from falling into the VFD.
- Tighten screws with proper torque.
- Keep combustible materials away from the VFD during maintenance.
- Do not perform isolation or pressure tests, or measure the control circuit with a megameter.
2.5 Device Disposal
- The VFD contains heavy metals and should be treated as industrial effluent.
- At the end of its life cycle, the product must enter the recycling system and be disposed of at an appropriate collection point, not in general waste.
3. Орнотуу
This chapter details the mechanical and electrical installation procedures for the VFD.
3.1 Механикалык орнотуу
The installation environment is critical for optimal performance and long-term stability. Ensure the following conditions are met:
| Environment Factor | Шарттар |
|---|---|
| Орнотуу сайты | Indoor |
| Курчап турган чөйрөнүн температурасы | -10°C to +40°C (temperature changing rate < 0.5°C/minute). Derate 1% for every additional 1°C above 40°C. Not recommended above 60°C. Provide cooling if in a closed space. External heating may be needed if restarting after a long stop in low temperatures. |
| Нымдуулук | RH≤90%, no condensation. Max relative humidity ≤ 60% in corrosive air. |
| Сактагыч | -40°C to +70°C (temperature changing rate < 1°C/minute). |
| Running environment condition | Keep away from electromagnetic radiation, contaminative air (corrosive gas, oil mist, flammable gas). Prevent foreign objects (metal powder, dust, oil, water) from entering. Do not install on flammable materials. Avoid direct sunlight, oil mist, steam, and vibration. |
| Бийиктик | Below 1000m (rated power). Derate 1% for every additional 100m between 1000m and 3000m. Configure isolation transformer above 2000m. Consult for altitudes between 3000m and 5000m. Do not use above 5000m. |
| Вибрация | ≤ 5.8m/s² (0.6g) |
| Орнотуу багыты | Upright position for sufficient cooling. |
The VFD should be installed in a clean, ventilated environment. Cooling air must be clean and free from corrosive materials and electrically conductive dust.
3.2 Installation Direction and Manner
The VFD can be installed on the wall or in a cabinet, always in an upright position. Refer to Appendix B for dimension drawings.
Wall-mounting steps:
- Mark the hole locations based on dimension drawings.
- Fix screws or bolts to the marked locations.
- Position the drive onto the wall.
- Бурамаларды бекем тартыңыз.
Ensure a minimum installation space of 100mm (A and B) around the VFD for proper airflow.

3.3 Электр монтаждоо
Proper electrical connections are vital for safe and reliable operation.
3.3.1 Connection Diagram of Main Circuit
The following diagram illustrates the main circuit connections. Optional parts like fuses, DC reactors, braking resistors, input/output reactors, and filters are available (refer to Appendix C).

Эскертүү: Remove yellow labels from PB, (+), and (-) terminal blocks before connecting braking resistor cables to ensure proper connection.
3.3.2 Terminals Figure of Main Circuit
The main circuit terminals are labeled as follows:
| Терминал белгиси | Терминал аты | Функция |
|---|---|---|
| R/L, S/N, T | Негизги схеманын кубаттуулугу | 3-phase/single-phase AC input terminals, generally connected with the grid. |
| У, В, В | VFD чыгаруу | 3-phase AC output terminals, generally connected with the motor. |
| PB, (+) | Тормоздук каршылык терминалы | PB and (+) are connected to the external resistor. |
| ⚧ | Жерге жайгаштыруу терминалы | Each machine has a standard PE terminal. |
Эскертүү: Do not use asymmetrically constructed motor cables. Route motor, input power, and control cables separately. The 'T' terminal cannot be wired in single-phase input.
3.3.3 Wiring of Terminals in Main Circuit
- Connect the ground wire of the input power cable to the VFD's ground terminal (PE), and the 3PH input cable to terminals R, S, and T. Fasten securely.
- Connect the ground wire of the motor cable to the VFD's ground terminal (PE), and the 3PH motor cable to terminals U, V, and W. Fasten securely.
- Connect the brake resistor and other accessories with cables to their specified positions.
- Fasten all cables outside the VFD mechanically, if possible.
3.3.4 Connection Diagram of the Control Circuit
The control circuit connections are detailed in the following diagram and table.

| Терминал | Description |
|---|---|
| ROA | RO relay output |
| ROC | Contactor capability: 3A/AC250V, 1A/DC30V |
| +10V | Жергиликтүү электр энергиясы +10 В |
| AI | 1. Input range: AI voltage and current: 0-10V/0-20mA (switch by J3) 2. Input impedance: voltage input: 20kΩ; current input: 500Ω 3. Resolution: 5mV (10V corresponds to 50Hz) 4. Deviation ±1%, 25°C Note: Keyboard potentiometer sets AI1 parameters, AI terminal sets AI2 parameters. |
| 24V | Жергиликтүү +24V электр менен камсыздоо, 100mA |
| GND | +10V шилтеме нөл потенциалы |
| AO | 1. Output range: 0-10V or 0-20mA 2. Томtage or current output depends on J2. |
| S1-S5 | Switch inputs 1-5. Internal impedance: 3.3kΩ. 0-4V for low electric level, 7-30V for high electric level. Max input frequency: 1kHz. All are programmable digital input terminals. |
| 485+, 485- | 485 communication interface and differential signal interface. Use twisted pairs or shielded cable. |
3.4 Wiring Protection
3.4.1 Protecting the VFD and Input Power Cable
Protect the VFD and input power cable from short circuits and thermal overload by arranging protection according to the following guidelines. Select the fuse as indicated in the manual. The fuse protects the input power cable and surrounding devices from short circuits.

3.4.2 Protecting the Motor and Motor Cables
The VFD protects the motor and motor cable in a short-circuit situation when the motor cable is dimensioned according to the rated current of the VFD. No additional protection devices are needed.
Эскертүү: If the VFD is connected to multiple motors, a separate thermal overload switch or circuit breaker must be used for protecting each cable and motor. These devices may require a separate fuse to cut off the short-circuit current.
3.4.3 Implementing a Bypass Connection
For continuous normal work of the VFD, especially in situations where faults may occur, it is necessary to set up power frequency and variable frequency conversion circuits. This allows the VFD to be bypassed if needed.
Эскертүү: Never connect the supply power to the VFD output terminals U, V, and W simultaneously with the AC power line. Power line voltage applied to the output can result in permanent damage to the VFD. If frequent shifting is required, use mechanically connected switches or contactors to ensure the motor terminals are not connected to the AC power line and VFD output terminals simultaneously.
4. Баскычтоптун иштеши
The keypad is used to control 280 series VFDs, read state data, and adjust parameters. An external keypad can be used with a standard RJ45 network cable.
4.1 Баскычтоптун сүрөттөмөсү

Эскертүү: The external keypad can be fixed with M3 screws or an optional installation bracket.
| Жок. | аты | Description |
|---|---|---|
| 1 | Мамлекеттик LED | RUN/TUNE: Off (stopping), Blinking (autotune), On (running). FWD/REV: Off (forward rotation), On (reverse rotation). LOCAL/REMOT: Off (keypad operation), Blinking (terminals operation), On (remote communication control). САПАР: On (fault state), Off (normal state), Blinking (overload pre-alarm). |
| 2 | LED бирдиги | Indicates the unit displayed (Hz, A, V, RPM, %). |
| 3 | Code displaying zone | 5-figure LED display for monitoring data and alarm codes. |
| 4 | Санариптик потенциометр | Corresponds to AI1. |
| 5 | Buttons | PRG/ESC: Enter/escape menu, remove parameter. DATA/ENT: Enter menu, confirm parameters. ЖОГОРУ / ТӨМӨН: Increase/decrease data or function code. Right-shift: Move right to select parameter/digit. ЖҮГҮРҮҮ: Operate VFD in key operation mode. STOP/RST: Stop VFD, reset control modes in fault alarm state. |
4.2 Keypad Display States
The keypad displays various states: stopping parameter, running parameter, function code editing, and fault alarm.
- Stopping Parameter State: Displays stopping parameters. Use P07.07 to select parameters. Use ►/SHIFT to shift parameters left-to-right, QUICK/JOG (P07.02=2) for right-to-left.
- Running Parameter State: After valid running commands, RUN/TUNE LED is on. FWD/REV LED indicates direction. Use P07.05 and P07.06 to select parameters. Use ►/SHIFT to shift parameters left-to-right, QUICK/JOG (P07.02=2) for right-to-left.
- Fault Display State: If a fault occurs, the keypad flickers with the fault code, and the TRIP LED is on. Fault reset can be done via STOP/RST button, control terminals, or communication commands.
- Function Codes Editing State: Press PRG/ESC to enter. Displays group number, tab, and set value. Use DATA/ENT to save, PRG/ESC to escape without saving. Parameters without flickering bits cannot be modified (e.g., detected parameters, running state parameters).
4.3 Modifying Function Codes
The VFD has three menu levels: group number, tab, and set value. Press PRG/ESC and DATA/ENT to return to the second-level menu. DATA/ENT saves parameters, PRG/ESC does not.
4.4 Орнотуу жана Viewing Password
- Паролду орнотуу: Set P7.00 to enable password protection. It becomes valid after exiting the editing state. Press PRG/ESC to enter the editing state, where '0.0.0.0.0' is displayed. Enter the correct password to access. Set P7.00 to 0 to disable.
- Viewing VFD State: Group P17 is for state inspection. Users can directly enter P17 to view the VFD's current state.
5. Function Parameters
The 280 series VFDs have function parameters organized into 30 groups (P00-P29), with P18-P28 reserved. Each group contains function codes with 3-level menus (e.g., P08.08 is the 8th function code in P8 group). P29 is factory reserved.
Parameters are described by: Function code, Name, Detailed description, Default value, and Modify status (○ for modifiable in stop/run, ● for not modifiable in run, ● for real detection value).
5.1 P00 Group: Basic Functions
This group covers fundamental settings for the VFD.
| Функция коду | аты | Description | Демейки маани | Өзгөртүү |
|---|---|---|---|---|
| P00.00 | Ылдамдыкты башкаруу режими | 2:SVPWM control (asynchronous motor), suitable for applications not requiring high control accuracy (e.g., fan/pump). One VFD can drive multiple motors. Note: Perform motor parameter autotuning before vector mode. | 2 | ○ |
| P00.01 | Иштеп жаткан буйруктардын каналы | Selects the source for run commands (start, stop, forward, reverse, jogging, fault reset). 0:Keypad running command channel (LOCAL/REMOT light off). 2:Communication running command channel (LOCAL/REMOT on). | 0 | ○ |
| P00.03 | Макс. чыгаруу жыштыгы | Sets the maximum output frequency. Foundation for frequency setting, acceleration/deceleration. Range: P00.04–400.00Hz. | 50.00Hz | ○ |
| P00.04 | Иштөө жыштыгынын жогорку чеги | Upper limit of output frequency, ≤ max. frequency. Range: P00.05–P00.03. | 50.00Hz | ○ |
| P00.05 | Lower limit of the running frequency | Lower limit of output frequency. VFD runs at this frequency if set frequency is lower. Range: 0.00Hz–P00.04. | 0.00Hz | ○ |
| P00.11 | ACC убактысы 1 | Time for VFD to speed up from 0Hz to Max. frequency (P00.03). Range: 0.0–3600.0s. | Моделине жараша | ○ |
| P00.12 | DEC убактысы 1 | Time for VFD to slow down from Max. frequency (P00.03) to 0Hz. Range: 0.0–3600.0s. | Моделине жараша | ○ |
| P00.13 | Жүгүрүү багытын тандоо | 0: Runs in default (forward) direction. FWD/REV indicator off. 1: Runs in opposite (reverse) direction. FWD/REV indicator on. 2: Forbid reverse direction. | 0 | ○ |
| P00.14 | Оператор жыштыгын жөндөө | Sets the carrier frequency. For 0.2-2.2kW motors, default is 4kHz. | Моделине жараша | ○ |
| P00.16 | AVR function selection | 0: Жараксыз 1: Valid during the whole process. Auto-adjusting function cancels impact of bus voltage fluctuation on output voltage. | 1 | ○ |
| P00.18 | Функцияны калыбына келтирүү параметри | 0: Операция жок 1: Restore default value 2: Clear fault records. Note: Restoring default value cancels user password. | 0 | ○ |
This is a partial list. For a complete list of function parameters, please refer to the official PDF manual: Колдонуучунун колдонмосу (PDF).
6. Fault Tracking
This section describes how to perform preventive maintenance and rectify faults on the VFD.
6.1 Fault Prevention: Maintenance Intervals
With proper environmental conditions, the VFD requires minimal maintenance. The following table outlines recommended routine maintenance intervals.
| Checking part | Текшерилүүчү нерсе | Текшерүү ыкмасы | Критерий |
|---|---|---|---|
| Айлана чөйрө | Temperature, humidity, vibration, dust, gas, oil fog, water drop | Visual examination and instrument test | Conforming to the manual |
| No foreign objects | Визуалдык экспертиза | No tools or dangerous objects | |
| Тtage | Main and control circuits normal | Measurement by multimeter | Conforming to the manual |
| Баскычтоп | Display clear and characters displayed totally | Визуалдык экспертиза | Characters displayed normally |
| Негизги схема | Screws tightened securely | Катуу | NA |
| No distortion, crackles, damage, color-changing from overheating/aging | Визуалдык экспертиза | NA | |
| No dust and dirtiness | Визуалдык экспертиза | NA (Note: copper block color change doesn't mean fault) | |
| Lead of conductors | No distortion or color-changing from overheating | Визуалдык экспертиза | NA |
| Terminals seat | No crackles, color-changing of protective layers, no damage, no weeping, crackles, cassis expansion | Визуалдык экспертиза | NA |
| Filter capacitors | Safety valve in right place, static capacity | Estimate usage time, measure static capacity | Static capacity ≥ 0.85 original value |
| Резисторлор | No replacement/splitting from overheating, no offline | Smelling, visual examination, remove one ending to coagulate or measure with multimeters | Resistors in ±10% of standard value |
| Transformers and reactors | No abnormal vibration, noise, smelling | Hearing, smelling, visual examination | NA |
| Electromagnetism contactors and relays | No vibration noise, contactor good enough, no loose screws/contactors | Hearing, visual examination, fasten up | NA |
| Control circuit (PCB and plugs) | No smelling, color-changing, crackles, damage, distortion, rust | Smelling, visual examination | NA |
6.2 Cooling Fan Maintenance
The VFD's cooling fan has a minimum life span of 25,000 operating hours. Operating hours can be found via P07.14. Increased noise from fan bearings indicates potential failure. Replace fans if symptoms appear, especially in critical applications.
Эскертүү: Follow safety precautions. Ignoring instructions may cause physical injury, death, or equipment damage.
Fan Replacement Steps:
- Stop the VFD and disconnect it from the AC power source. Wait for the designated time.
- Lever the fan holder off the drive frame with a screwdriver and lift it slightly.
- Disconnect the fan cable.
- Remove the fan holder from the hinges.
- Install the new fan holder in reverse order, ensuring the wind direction is consistent with the VFD.
- Күчтү калыбына келтириңиз.
6.3 Capacitors and Power Cable
6.3.1 Reforming Capacitors
If the VFD has been stored for a long time, the DC bus capacitors must be reformed. The storing time is counted from the production date (marked in the serial number).
| Убакыт | Иштөө принциби |
|---|---|
| Storing time less than 1 year | Operation without charging |
| Storing time 1-2 years | Connect with the power for 1 hour before first ON command |
| Storing time 2-3 years | Use power surge to charge for the VFD: • Add 25% rated voltage 30 мүнөткө • Add 50% rated voltage 30 мүнөткө • Add 75% rated voltage 30 мүнөткө • Add 100% rated voltage 30 мүнөткө |
| Storing time more than 3 years | Use power surge to charge for the VFD: • Add 25% rated voltage for 2 hours • Add 50% rated voltage for 2 hours • Add 75% rated voltage for 2 hours • Add 100% rated voltage for 2 hours |
Жогорку тtage VFDs (e.g., 380V) require sufficient voltage during charging. Small capacitor power (2A) can be used.
6.3.2 Changing Electrolytic Capacitors
Эскертүү: Follow safety precautions. Ignoring instructions may cause physical injury, death, or equipment damage.
Change electrolytic capacitors if their working hours exceed 35,000. Contact local INVT offices for detailed operation.
6.3.3 Power Cable Maintenance
Эскертүү: Follow safety precautions. Ignoring instructions may cause physical injury, death, or equipment damage.
- Stop the drive and disconnect it from the power line. Wait for the designated time.
- Check the tightness of the power cable connections.
- Күчтү калыбына келтириңиз.
6.4 Fault Rectification
Faults are indicated by LEDs. The TRIP light on, or an alarm/fault message on the panel display, indicates an abnormal VFD state. P07.27–P07.32 record the last 6 fault types, and P07.33–P07.56 record operation data for the last 3 fault types. Use this information to identify and correct most alarms and faults. If issues persist, contact INVT.
6.4.1 Мүчүлүштүктөрдү калыбына келтирүү
The VFD can be reset by pressing the keypad's STOP/RST key, via digital input, or by cycling power. Once the fault is cleared, the motor can be restarted.
6.4.2 Fault Instruction and Solution
After a VFD fault:
- Check the keypad for issues.
- If no keypad issues, check P07 for recorded fault parameters to confirm the real state.
- Refer to the fault table below for detailed solutions.
- Eliminate the fault and reset.
| Ката коду | Ката түрү | Мүмкүн болгон себеп | Эмне кылуу керек |
|---|---|---|---|
| OC1 | Over-current when acceleration | 1. Acceleration too fast 2. Grid voltage өтө төмөн 3. VFD power too low 4. Load transients/abnormal 5. Grounding short circuit/phase loss 6. Strong external interference | 1. Increase ACC time 2. Check input power 3. Select larger VFD 4. Check for short circuits/smooth rotation 5. Check output configuration 6. Check for strong interference |
| OC2 | Over-current when deceleration | Same as OC1 | Same as OC1 |
| OC3 | Over-current when constant speed running | Same as OC1 | Same as OC1 |
| OV1 | Көлөмүtage when acceleration | 1. Анормалдуу кириш томtage 2. Large energy feedback | 1. Check input power 2. Check DEC time/VFD starts during rotation |
| OV2 | Көлөмүtage when deceleration | Same as OV1 | Same as OV1 |
| OV3 | Көлөмүtage when constant speed running | Same as OV1 | Same as OV1 |
| UV | DC bus Under-voltage | Электр менен камсыздоо көлөмүtage өтө төмөн | Check input power supply line |
| OL1 | Мотор ашыкча жүктөө | 1. Электр энергиясы менен камсыз кылуу тtage өтө төмөн 2. Motor setting rated current incorrect 3. Motor stall or load transients too strong | 1. Check power supply line 2. Reset rated current 3. Check load and adjust torque lift |
| OL2 | VFD ашыкча жүктөө | 1. Acceleration too fast 2. Reset rotating motor 3. Электр энергиясы менен камсыз кылуу тtage өтө төмөн 4. Load too heavy 5. Motor power too small | 1. Increase ACC time 2. Avoid restarting after stopping 3. Check power supply line 4. Select VFD with bigger power 5. Select proper motor |
| OL3 | Электрдик ашыкча жүктөө | VFD reports overload pre-alarm according to set value | Check load and overload pre-alarm point |
| OH1 | Rectifier overheated | 1. Air duct jam or fan damage 2. Абанын температурасы өтө жогору 3. Overload running time too long | 1. Refer to overcurrent solution 2. Redistribute/dredge wind channel or change fan 3. Айлана-чөйрөнүн температурасын төмөндөтүү 4. Check and reconnect 5. Change power 6. Change power unit 7. Change main control panel |
| OH2 | Inverter module overheated | Same as OH1 | Same as OH1 |
| EF | Тышкы күнөө | SI external fault input terminals action | Check external device input |
| CE | Байланыш катасы | 1. Baud rate setting incorrect 2. Fault in communication wiring 3. Communication address wrong 4. Strong interference | 1. Set proper baud rate 2. Check communication connection 3. Set proper communication address 4. Change/replace connection or improve anti-interference capability |
| EEP | EEPROM катасы | 1. Error controlling read/write parameters 2. Damage to EEPROM | 1. Press STOP/RST to reset 2. Change main control panel |
| PIDE | PID feedback fault | 1. PID feedback offline 2. PID feedback source disappear | 1. Check PID feedback signal 2. Check PID feedback source |
| END | Time reach of factory setting | Actual running time of VFD exceeds internal setting | Ask supplier to adjust setting running time |
| LL | Электрондук аз жүктөө катасы | VFD reports underload pre-alarm according to set value | Check load and underload pre-alarm point |
7. Байланыш протоколу
This chapter introduces the Modbus protocol and its application with the VFD.
7.1 Modbus Protocol Introduction
Modbus is a software protocol for electrical controllers, enabling communication between devices over a network (e.g., RS485). It allows controlling devices from different manufacturers to be connected and monitored. There are two transmission modes: ASCII and RTU. All devices on a Modbus network must use the same transmission mode and basic parameters (baud rate, digital bit, check bit, stopping bit).
Modbus operates with a single master and multiple slaves. The master sends messages, and slaves respond. The VFD can be configured as a slave. The master can communicate with a single slave or broadcast to all. A single-visiting command requires a response, while broadcasting does not.
7.2 Application Mode for the VFD
The VFD's Modbus protocol uses RTU mode with a 2-wire RS485 physical layer.
7.2.1 Two-wire RS485
The 2-wire RS485 interface operates in half-duplex mode, using differential transmission (A(+) and B(-)). A(+) and B(-) on the terminal board correspond to 485+ and 485-. Baud rate determines transmission speed; higher baud rates mean faster communication but weaker anti-interference. For 0.56mm (24AWG) twisted pairs, the maximum transmission distance is:
| Бод ылдамдыгы | Макс. берүү аралык |
|---|---|
| 2400BPS | 1800 м |
| 4800BPS | 1200 м |
| 9600BPS | 800 м |
| 19200BPS | 600 м |
Shielded cables are recommended for RS485 remote communication, with the shield layer used as grounding wires. For shorter distances and fewer devices, a 120Ω terminal resistor is recommended.
7.2.2 Single Application
For a single VFD and PC Modbus connection, an RS232 or USB to RS485 converter is typically used. Connect the A terminal of RS485 to 485+ on the VFD and B to 485-. Use shielded twisted pairs. Keep converter wire lengths short (within 15m for RS232-RS485). Select the correct interface and set communication parameters (baud rate, digital check bit) to match the VFD.
7.2.3 Multi-application
In multi-application scenarios, chrysanthemum and star connections are common. Chrysanthemum chain connection is required by RS485 industrial fieldbus standards, with 120Ω terminal resistors at both ends.
7.3 RTU режими
7.3.1 RTU Communication Frame Format
In RTU mode, each 8-bit byte in the message includes two 4-bit hex characters, allowing more data transmission at the same baud rate compared to ASCII mode. A frame includes a start bit, 7 or 8 digital bits, an even/odd check bit (optional), and an end bit. The data format is illustrated below:
| Баштоо бит | BIT1 | BIT2 | BIT3 | BIT4 | BIT5 | BIT6 | BIT7 | BIT8 | Текшерүү бит | End bit |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Маалыматтар | Маалыматтар | Маалыматтар | Маалыматтар | Маалыматтар | Маалыматтар | Маалыматтар | Маалыматтар | Паритет | 1 |
A new frame starts after an idle time of 3.5 bytes. The frame structure includes slave address, operation command code, data, and CRC check character. The standard RTU frame structure is:
| Талаа | Description |
|---|---|
| START | T1-T2-T3-T4 (transmission time of 3.5 bytes) |
| ADDR | Communication address: 0-247 (0 is broadcast address) |
| CMD | 03H: read slave parameters; 06H: write slave parameters |
| DATA (N-1)...DATA (0) | Main content of communication (2*N bytes) |
| CRC CHK low bit / high bit | Detection value: CRC (16BIT) |
| END | T1-T2-T3-T4 (transmission time of 3.5 bytes) |
7.3.2 RTU Communication Frame Error Checkout
Error checkout is essential due to potential data transmission errors (e.g., electromagnetic interference). It involves bit checkout of the byte and CRC check of the entire frame.
- Bit checkout: Even or odd check bits are added to stabilize parity.
- CRC текшерүү: A 16-figure binary value is added to the frame. The receiving device recalculates and compares it to detect errors.
7.4 RTU Command Code and Communication Data Description
7.4.1 Command Code: 03H (Read N words)
This command reads data from the VFD. The number of words to read depends on the 'data number' in the command code (max 16 words). Each data byte is 2 (one word). Example: reading 2 data contents from 0004H from VFD with address 01H.
7.4.2 Command Code: 06H (Write one word)
This command writes data to the VFD, changing its working mode. Example: writing 5000 (1388H) to 0004H from VFD with address 02H.
7.4.3 Command Code: 08H for Diagnosis
Sub-function code 0000 returns inquiry information data. The inquiry information string is the same as the response information string when loop detection to address 01H of the driver is carried out.
7.4.4 Definition of Data Address
The data address controls VFD running and retrieves state information/function parameters. The parameter address occupies 2 bytes (high bit in front, low bit behind). The high byte is the group number before the radix point, and the low byte is the number after the radix point (both converted to hex).
Эскертүү: P29 group is a factory parameter and cannot be read or changed. Some parameters cannot be changed while the VFD is running. EEPROM is frequently stocked, which may shorten its usage time. Some functions can be met by changing the value in RAM.
7.5 Fieldbus Ratio Values
Communication data is expressed in hex. Non-integers are magnified by a multiple to get an integer, called fieldbus ratio values. These values refer to the radix point of the setting range or default value in the function parameter list. If there are figures behind the radix point (n=1), the fieldbus ratio value 'm' is 10^n.
7.6 Fault Message Response
If a fault occurs during communication control (e.g., a parameter can only be read), the VFD will return a fault response message. The message includes a code and its meaning.
| Code | аты | Мааниси |
|---|---|---|
| 01H | Мыйзамсыз буйрук | Command cannot be executed (e.g., new version only, VFD in fault state). |
| 02H | Мыйзамсыз маалымат дареги | Operation address invalid or not allowed (e.g., register/transmitting bytes combination invalid). |
| 03H | Illegal value | Invalid data in received message frame (not data value out of range). |
| 04H | Операция ишке ашкан жок | Parameter setting in parameter writing invalid (e.g., function input terminal set repeatedly). |
| 05H | Сырсөз катасы | Password written to check address does not match set password. |
| 06H | Data frame error | Length of digital frame incorrect or CRC check bit differs. |
| 07H | Written not allowed | Written data exceeds parameter range, parameter not modifiable, or terminal already used. |
| 08H | Parameter cannot be changed during running | Modified parameter in writing cannot be modified during running. |
| 09H | Сырсөз менен коргоо | User password set without unlocking. |
8. Техникалык маалыматтар
This appendix provides technical data related to derating, CE marking, and EMC regulations.
8.1 Derating in Application
8.1.1 Кубаттуулугу
VFD sizing is based on rated motor current and power. The VFD's rated current and power must be greater than or equal to the motor's. Power ratings are consistent within a voltage диапазону.
Эскертүү: Maximum allowed motor shaft power is limited to 1.5*PN. The ratings apply at 40°C ambient temperature. In common DC systems, ensure power through the DC connection does not exceed PN.
8.1.2 Детинг
Load capacity decreases if ambient temperature exceeds 40°C, altitude exceeds 1000 meters, or carrier frequency changes (from 4 kHz to 8, 12, or 15 kHz).
8.1.2.1 Temperature-based Derating
Between +40°C and +50°C, the rated output current decreases by 1% for every additional 1°C. It is not recommended to use the VFD above 50°C.

8.1.2.2 Altitude-based Derating
Below 1000m, the VFD runs at rated power. Above 1000m, allowable output power is derated. For altitudes above 2000m, an isolation transformer is required. For altitudes between 3000m and 5000m, consult the manufacturer. Do not use above 5000m.
8.1.2.3 Carrier Frequency-based Derating
The rated power is defined by its factory carrier frequency. The VFD must derate 10% for every additional 1kHz carrier frequency if it exceeds the factory value.
8.2 CE and EMC Regulations
8.2.1 CE маркасы
The CE mark indicates compliance with European Low Voltage (2006/95/EC) and EMC Directives (2004/108/EC).
8.2.2 Compliance with European EMC Directive
The EMC Directive sets requirements for immunity and emissions of electrical equipment. The EMC product standard (EN 61800-3:2004) covers drive requirements.
8.2.3 EMC Regulations
The EMC product standard (EN 61800-3:2004) defines EMC requirements for VFDs, categorizing environments and VFD types:
- First environment: Domestic environment (low-voltage network for domestic purposes).
- Second environment: Not directly supplying domestic premises.
VFD Categories:
- C1: Рейтингдүү томtage < 1000V, used in the first environment.
- C2: Рейтингдүү томtage < 1000V, used in the first environment, installed by professional electrician.
- C3: Рейтингдүү томtage < 1000V, used in the second environment.
- C4: Рейтингдүү томtage > 1000V or nominal current ≥ 400A, used in complicated systems in the second environment.
8.2.3.1 Category C2
Emission limits are met by:
- Selecting and installing optional EMC filter as specified.
- Selecting motor and control cables as specified.
- Installing the drive according to instructions.
Эскертүү: In a domestic environment, this product may cause radio interference, requiring supplementary mitigation measures.
8.2.3.2 Category C3
Immunity performance complies with IEC/EN 61800-3. Emission limits are met by:
- Selecting and installing optional EMC filter as specified.
- Selecting motor and control cables as specified.
- Installing the drive according to instructions.
Эскертүү: A Category C3 drive is not intended for low-voltage public networks supplying domestic premises. Radio frequency interference is expected if used on such a network.
9. Peripheral Options and Parts
This appendix describes how to select and wire peripheral options and parts for 280 series VFDs.
9.1 Peripheral Wiring
The following diagram shows the peripheral wiring for 280 series VFDs, including connections for power supply, breaker, input reactor, input filter, keypad, PC, brake resistor, output filter, output reactor, and motor.

| Сүрөт | аты | Description |
|---|---|---|
![]() | Кабельдер | Device to transfer the electronic signals. |
![]() | Breaker | Prevents electric shock and protects power supply/cables from overcurrent. Select breaker with high-order harmonic reduction and rated sensitive current > 30mA. |
![]() | Киргизүүчү реактор | Improves power factor, controls higher harmonic current. VFDs > 37kW can connect with DC reactor. |
![]() | Киргизүү чыпкасы | Controls electromagnetic interference from VFD. Install close to input terminal. |
![]() | Тормоздук резисторлор | Shortens DEC time. |
![]() | Чыгуу чыпкасы | Controls interference from output side. Install close to output terminals. |
![]() | Чыгуу реактору | Prolongs effective transmitting distance, controls sudden high voltage when switching inverter unit. |
9.2 Электр энергиясы
Эскертүү: Check that the VFD's voltage degree complies with the supply power voltage.
9.3 Кабельдер
9.3.1 Электр кабелдери
Dimension input power and motor cables according to local regulations. A separate PE conductor is required if the cable shield's conductivity is insufficient.
9.3.2 Башкаруу кабелдери
All analog control cables and frequency input cables must be shielded. Relay cables need braided metallic screen. Run analog and digital signals in separate cables. Check input power cable insulation before connecting.
| VFD модели | Recommended cable size (mm²) RST UVW | Recommended cable size (mm²) PE | Connecting cable size (mm²) RST UVW | Connecting cable size (mm²) P1 and (+) | Connecting cable size (mm²) PB (+) and (-) | Connecting cable size (mm²) PE | Terminal screw size | Катуу моменти (Нм) |
|---|---|---|---|---|---|---|---|---|
| 280-G0.2KW-S2 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | M3 | 0.56 |
| 280-G0.4KW-S2 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | M3 | 0.56 |
| 280-G0.75KW-S2 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | M3 | 0.56 |
| 280-G1.5KW-S2 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | M3 | 0.8 |
| 280-G2.2KW-S2 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | M3 | 0.8 |
| 280-G0.2KW-B2 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | M3 | 0.56 |
| 280-G0.4KW-B2 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | M3 | 0.56 |
| 280-G0.75KW-B2 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | M3 | 0.56 |
| 280-G1.5KW-B2 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | M3 | 0.8 |
| 280-G2.2KW-B2 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | M3 | 0.8 |
| 280-G0.75KW-B3 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | M3 | 0.8 |
| 280-G1.5KW-B3 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | M3 | 0.8 |
| 280-G2.2KW-B3 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | M3 | 0.8 |
Эскертүү: Use recommended cable size for 40°C and rated current. Wiring distance should be ≤ 100m. Terminals P1, (+), PB, and (-) connect DC reactor options and parts.
9.4 Breaker and Electromagnetic Contactor
Fuses are necessary for overload protection. Use a breaker (MCCB) compliant with the VFD power in 3-phase AC. Breaker capacity should be 1.5-2 times the rated current.
Эскертүү: Hot ionized gases may escape from the breaker enclosure during a short-circuit. Follow manufacturer's instructions for installation and placement.
An electromagnetic contactor should be installed on the input side to control switching on/off and ensure safety in case of system fault.
| VFD | Сактагыч (A) | Бөлгүч (A) | Rated working current of the contactor (A) |
|---|---|---|---|
| 280-G0.2KW-S2 | 16 | 10 | 10 |
| 280-G0.4KW-S2 | 16 | 16 | 10 |
| 280-G0.75KW-S2 | 16 | 16 | 16 |
| 280-G1.5KW-S2 | 25 | 25 | 16 |
| 280-G2.2KW-S2 | 50 | 40 | 32 |
| 280-G0.2KW-B2 | 6 | 6 | 6 |
| 280-G0.4KW-B2 | 6 | 10 | 10 |
| 280-G0.75KW-B2 | 10 | 10 | 10 |
| 280-G1.5KW-B2 | 25 | 16 | 16 |
| 280-G2.2KW-B2 | 32 | 25 | 16 |
| 280-G0.75KW-B3 | 10 | 6 | 10 |
| 280-G1.5KW-B3 | 10 | 10 | 10 |
| 280-G2.2KW-B3 | 16 | 16 | 10 |
9.5 Reactors
Transient high current in the input power circuit can damage rectifying components. AC reactors on the input side prevent high-voltage input and improve power factors.
If the distance between the VFD and motor exceeds 50m, parasitic capacitance can cause large leakage current and frequent overcurrent protection. An output reactor must be added to prevent this and motor insulator damage. For distances between 50m and 100m, select the reactor from the table below. For distances over 100m, contact technical support.
| VFD | Киргизүүчү реактор | Чыгуу реактору |
|---|---|---|
| 280-G0.2KW-B2 | ACL2-1R5-4 | OCL2-1R5-4 |
| 280-G0.4KW-B2 | ACL2-1R5-4 | OCL2-1R5-4 |
| 280-G0.75KW-B2 | ACL2-2R2-4 | OCL2-2R2-4 |
| 280-G0.75KW-B3 | ACL2-1R5-4 | OCL2-1R5-4 |
| 280-G1.5KW-B3 | ACL2-1R5-4 | OCL2-1R5-4 |
| 280-G2.2KW-B3 | ACL2-2R2-4 | OCL2-2R2-4 |
Эскертүү: Rated derate voltage of input reactor is 2%±15%. Power factor of input side is >90% after adding DC reactor. Rated derate voltage of output reactor is 1%±15%. These options are external and must be specified when purchasing.
9.6 Фильтрлер
Input interference filters reduce VFD interference to surrounding equipment. Output interference filters reduce radio noise from cables and leakage current. The company provides various filters for user convenience.
9.6.1 C3 Filter Type Instruction
The filter type designation (e.g., FLT-P 04 003 L - C - G) provides detailed information:
| Character designation | Толук инструкция |
|---|---|
| A | FLT: VFD чыпкасы сериясы |
| B | Filter type: P: power supply filter, L: output filter |
| C | Тtage degree: S2: AC 1PH 220V(-15%) – 240V(+10%), 04: AC 3PH 380V (-15%) – 440V(+10%) |
| D | 3-digit development serial number (e.g., 003 for C3 filters) |
| E | Installation type: L: Common type, H: High performance type |
| F | Utilization environment of the filters: A: first environment (C1), B: first environment (C2), C: second environment (C3) |
| G | Special for external C3 filter |
9.6.2 C3 Filters
When selecting C3 input filters, parallel-connect the filter to the VFD input.
| VFD | Киргизүү чыпкасы |
|---|---|
| 280-G0.2KW-S2 | FLT-PS2005L-C-G |
| 280-G0.4KW-S2 | FLT-PS2005L-C-G |
| 280-G0.75KW-S2 | FLT-PS2005L-C-G |
| 280-G1.5KW-S2 | FLT-PS2010L-C-G |
| 280-G2.2KW-S2 | FLT-PS2010L-C-G |
| 280-G0.2KW-B2 | FLT-P04008L-C-G |
| 280-G0.4KW-B2 | FLT-P04008L-C-G |
| 280-G0.75KW-B2 | FLT-P04008L-C-G |
| 280-G1.5KW-B2 | FLT-P04006L-C-G |
| 280-G2.2KW-B2 | FLT-P04006L-C-G |
| 280-G0.75KW-B3 | FLT-P04006L-C-G |
| 280-G1.5KW-B3 | FLT-P04006L-C-G |
| 280-G2.2KW-B3 | FLT-P04006L-C-G |
9.6.3 C2 Filter Type Instruction
The filter type designation (e.g., FLT-P 04 016 L - B) provides detailed information:
| Character designation | Толук инструкция |
|---|---|
| A | FLT: VFD чыпкасы сериясы |
| B | Filter type: P: power supply filter, L: output filter |
| C | Тtage degree: S2: AC 1PH 220V(-15%) – 240V(+10%), 04: AC 3PH 380V (-15%) – 440V(+10%) |
| D | 3-bit rated current code (e.g., "016" means 16A) |
| E | Installation type: L: Common type, H: High performance type |
| F | Utilization environment of the filters: A: first environment (C1), B: first environment (C2) |
9.6.4 C2 Filters
| VFD | Киргизүү чыпкасы | Чыгуу чыпкасы |
|---|---|---|
| 280-G0.2KW-S2 | FLT-PS2010H-A | FLT-L02010H-A |
| 280-G0.4KW-S2 | FLT-PS2010H-A | FLT-L02010H-A |
| 280-G0.75KW-S2 | FLT-PS2010H-A | FLT-L02010H-A |
| 280-G1.5KW-S2 | FLT-P04016L-B | FLT-L04016L-B |
| 280-G2.2KW-S2 | FLT-P04032L-B | FLT-L04032L-B |
| 280-G0.2KW-B2 | FLT-P04006L-B | FLT-L04006L-B |
| 280-G0.4KW-B2 | FLT-P04006L-B | FLT-L04006L-B |
| 280-G0.75KW-B2 | FLT-P04006L-B | FLT-L04006L-B |
| 280-G1.5KW-B2 | FLT-P04016L-B | FLT-L04016L-B |
| 280-G2.2KW-B2 | FLT-P04016L-B | FLT-L04016L-B |
| 280-G0.75KW-B3 | FLT-P04006L-B | FLT-L04006L-B |
| 280-G1.5KW-B3 | FLT-P04006L-B | FLT-L04006L-B |
| 280-G2.2KW-B3 | FLT-P04016L-B | FLT-L04016L-B |
Эскертүү: Input EMI meets C2 requirements after adding input filters. These options are external and must be specified when purchasing.
9.7 Тормоздоо системасы
9.7.1 Brake Units
280 series products do not include brake units. If a brake unit is required, select one according to the lot number.
9.7.2 Selecting Brake Components
If the motor's rotating speed exceeds the reference frequency, it acts as a generator, returning inertial energy to the VFD's DC circuit. This can cause voltage increases and damage. Braking resistors are necessary to prevent this.
Эскертүү: Only qualified electricians should design, install, commission, and operate the VFD. Follow all warnings. Incorrect wiring can damage the VFD or braking options. Do not connect the braking resistor to terminals other than PB and (-).
Эскертүү: Never use a brake resistor with resistance below the minimum specified value. The drive and internal chopper cannot handle overcurrent from low resistance. Increase braking resistor power for frequent braking situations (frequency usage ratio > 10%).
| Модел | Braking resistor at 100% of the braking torque (Ω) | Dissipation power (kW) 10% braking | Dissipation power (kW) 50% braking | Dissipation power (kW) 80% braking | Mini braking resistor (Ω) |
|---|---|---|---|---|---|
| 280-G0.2KW-S2 | 722 | 0.03 | 0.15 | 0.24 | 42 |
| 280-G0.4KW-S2 | 361 | 0.06 | 0.30 | 0.48 | 42 |
| 280-G0.75KW-S2 | 192 | 0.11 | 0.56 | 0.90 | 42 |
| 280-G1.5KW-S2 | 96 | 0.23 | 1.1 | 1.8 | 30 |
| 280-G2.2KW-S2 | 65 | 0.33 | 1.7 | 2.6 | 21 |
| 280-G0.2KW-B2 | 722 | 0.03 | 0.15 | 0.24 | 42 |
| 280-G0.4KW-B2 | 361 | 0.06 | 0.30 | 0.48 | 42 |
| 280-G0.75KW-B2 | 192 | 0.11 | 0.56 | 0.90 | 42 |
| 280-G1.5KW-B2 | 96 | 0.23 | 1.1 | 1.8 | 30 |
| 280-G2.2KW-B2 | 65 | 0.33 | 1.7 | 2.6 | 21 |
| 280-G0.75KW-B3 | 653 | 0.11 | 0.6 | 0.9 | 100 |
| 280-G1.5KW-B3 | 326 | 0.23 | 1.1 | 1.8 | 100 |
| 280-G2.2KW-B3 | 222 | 0.33 | 1.7 | 2.6 | 54 |
Эскертүү: Select resistor and power based on provided data. The table shows values for 100% braking torque, 10%, 50%, and 80% braking usage rate.
9.7.3 Placing the Brake Resistor
Install all resistors in a well-cooled place.
Эскертүү: Materials near the brake resistor must be non-flammable. The resistor's surface temperature is high, and airflow can reach hundreds of degrees Celsius. Protect the resistor from contact.
Only external braking resistors are needed for the 280 series.

10. Өлчөмдөрдүн чиймелери
This appendix provides dimension drawings for the 280 series VFDs, with dimensions in millimeters and inches.
10.1 Keypad Structure

The keypad can be externally installed on an optional bracket. The cut-out for keypad installation without brackets is also provided.
10.2 VFD Chart (Wall Mounting)

| Модел | W1 | W2 | H1 | H2 | D |
|---|---|---|---|---|---|
| 280-G0.2KW-S2 | 85.0 | 74.0 | 145.5 | 131.5 | 134.2 |
| 280-G0.4KW-S2 | 85.0 | 74.0 | 145.5 | 131.5 | 134.2 |
| 280-G0.75KW-S2 | 85.0 | 74.0 | 145.5 | 131.5 | 153.2 |
| 280-G1.5KW-S2 | 100.0 | 89.0 | 170.5 | 154.0 | 153.2 |
| 280-G2.2KW-S2 | 100.0 | 89.0 | 170.5 | 154.0 | 153.2 |
| 280-G0.2KW-B2 | 85.0 | 74.0 | 145.5 | 131.5 | 134.2 |
| 280-G0.4KW-B2 | 85.0 | 74.0 | 145.5 | 131.5 | 134.2 |
| 280-G0.75KW-B2 | 85.0 | 74.0 | 145.5 | 131.5 | 153.2 |
| 280-G1.5KW-B2 | 100.0 | 89.0 | 170.5 | 154.0 | 153.2 |
| 280-G2.2KW-B2 | 100.0 | 89.0 | 170.5 | 154.0 | 153.2 |
| 280-G0.75KW-B3 | 100.0 | 89.0 | 170.5 | 154.0 | 153.2 |
| 280-G1.5KW-B3 | 100.0 | 89.0 | 170.5 | 154.0 | 153.2 |
| 280-G2.2KW-B3 | 100.0 | 89.0 | 170.5 | 154.0 | 153.2 |
11. Колдонуучунун кеңештери
- Туура өлчөм: Always ensure the VFD's rated current and power are equal to or higher than the motor's requirements to prevent overload and ensure optimal performance.
- Экологиялык маалымдуулук: Pay close attention to ambient temperature and altitude. If operating outside recommended ranges, apply the specified derating factors or provide additional environmental controls (e.g., cooling fans, heating devices) to prevent damage.
- Кабелдик башкаруу: Use shielded cables for control signals and ensure proper grounding. Route power and control cables separately to minimize interference.
- Үзгүлтүксүз текшерүүлөр: Periodically inspect terminals for tightness, check for any signs of overheating or damage, and ensure the cooling fan is operating correctly. Early detection of issues can prevent larger problems.
- Modbus байланышы: When setting up Modbus, ensure all devices share the same baud rate and communication parameters. Verify communication addresses are unique for each slave device.
12. Кепилдик жана колдоо
For product and service inquiries, please contact your local INVT office. You can find a list of INVT offices and contact information on www.invt.com.
Your feedback on INVT VFD manuals is welcome. You can provide feedback by visiting the website or contacting online service personnel.
An online document library is available for manuals and other product documents in PDF format. Visit the website and navigate to 'Service and Support > Data Download'.
For further assistance, please refer to the official PDF manual: Колдонуучунун колдонмосу (PDF).