1. Киришүү
The SINOTIMER STVP series automatic over-voltagе жана ылдый-томtage protector is designed for three-phase 3*127V/220VAC power systems with a rated working current of 80A. This device provides essential protection for electrical equipment by instantaneously cutting off the power supply when over-voltage, томдун астындаtage, or over-current conditions are detected. Once the circuit voltage returns to normal, the protector automatically restores power, ensuring continuous operation and safeguarding your appliances from damage.
This protector integrates multiple protection functions including over-voltage, томдун астындаtage, over-current, three-phase current (voltage) imbalance, phase sequence (reverse phase), zero-break, and phase-break protection. It also features voltmeter and ammeter functions, and the ability to restore factory settings. The device offers comprehensive features, stable performance, and ease of operation.
PDF форматындагы деталдуу колдонуучу колдонмону жүктөп алуу үчүн жеткиликтүү: Колдонуучунун колдонмосу (PDF)
2. Негизги өзгөчөлүктөрү
- Көлөмүtagд коргоо
- Көлөмдүн астындаtagд коргоо
- Ашыкча ток коргоо
- Автоматтык калыбына келтирүү
- Тtage display (separate ABC phase voltagд өлчөө)
- Ampere display (separate ABC phase ampere measurement)
- Үч фазалуу ampere unbalance protection
- Phase sequence protection (reverse phase protection)
- Zero line break protection
- Фазалык бузулуулардан коргоо
- Fault inquiry function
- Rotation display of voltage and current for each phase
- Adjustable over-voltage protection value and recovery value
- Adjustable under-voltage protection value and recovery value
- Adjustable over-current protection value and action time
- Adjustable 3-phase ampere unbalance protection value and action time
- Adjustable delay time after power-on
- Жөнгө салынуучу катаны калыбына келтирүү кечиктирүү убактысы
- Factory data reset function
3. Продукттун спецификациялары
| Атрибут | Нарк |
|---|---|
| Модель номери | STVP936-1-80A |
| Электр камсыздоо | 3*127V/220VAC 60Hz |
| Rated Voltage | 220V |
| Фаза | Үч фазалуу |
| Max. Учурдагы жүктөө | 1~80A Adjustable (default: 80A) |
| Көлөмүtage Коргоо диапазону | 121V-150V-OFF Adjustable (default: 140V) |
| Көлөмүtage калыбына келтирүү диапазону | 120V-149V (default: 135V) |
| Көлөмүtage Иш-аракет убактысы | 0.1~10 seconds (default: 0.2s) |
| Көлөмдүн астындаtage Коргоо диапазону | 118V-80V-OFF Adjustable (default: 90V) |
| Көлөмдүн астындаtage калыбына келтирүү диапазону | 118V-91V (default: 95V) |
| Көлөмдүн астындаtage Иш-аракет убактысы | 0.1~10 seconds (default: 0.2s) |
| 3-Phase Volt Unbalance Protection | 10%~50%~OFF (default: 20%) |
| 3-Phase Volt Unbalance Action Time | 0.1~10 seconds (default: 1s) |
| Delay Time After Power-on | 2~255 seconds (default: 2s) |
| Fault Recovery Delay Time | 2~600 seconds (default: 60s) |
| Дисплей модели | LCD |
| Өлчөмдөр | 71.5mm (W) * 95.2mm (H) * 65.7mm (D) |
| Орнотуу | 35 мм DIN темир жол |
| Сертификация | CE, RoHS |
4. Коопсуздук маалыматы
- Орнотуу жана тейлөө квалификациялуу электриктер тарабынан гана аткарылышы керек.
- Ensure the power supply is disconnected before any installation or wiring work.
- The device does not provide overload or short-circuit protection. It must be used in conjunction with appropriate external circuit breakers (e.g., C45, C65 mini circuit breakers) for comprehensive protection.
- Кубатты колдонуудан мурун бардык зымдарды туташтыруу коопсуз жана туура экендигин текшериңиз.
- Do not operate the device in wet or hazardous environments.
5. Орнотуу
5.1 Физикалык өлчөмдөр

5.2 Монтаждоо
The protector is designed for 35mm DIN rail installation. Snap the device onto the DIN rail securely.

5.3 Электр өткөргүч схемасы
Connect the input and output terminals as shown in the diagram below. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The input terminals are located at the top, and output terminals at the bottom.


6. Орнотуу жана конфигурациялоо
Орнотуу режимине кирүү үчүн басып, кармап туруңуз SET button for 3 seconds. Then, continuously press SET to cycle through the parameters. Use the ▲ жана ▼ buttons to adjust the values. When "ENd" appears, press SET again to save the data and exit the setting mode.
If no operation is performed within 10 seconds after pressing SET, the device will automatically exit the setting mode, and any unsaved changes will be lost.
6.1 Parameter Settings Table
| Кадам | Мазмун | LCD дисплей | Description / Range (Default) |
|---|---|---|---|
| 1 | Көлөмүtage коргоо мааниси | Uvo 280V | 221V-300V-OFF (280V) |
| 2 | Көлөмүtage калыбына келтирүү мааниси | Uvor 250V | 220V-299V (250V) |
| 3 | Көлөмүtage коргоо иш-аракет убактысы | 0.2S | 0.1-10с (0.2сек.) |
| 4 | Көлөмдүн астындаtage коргоо мааниси | Uve 160V | 219V-150V-OFF (160V) |
| 5 | Көлөмдүн астындаtage калыбына келтирүү мааниси | Uver 180V | 151V-220V (180V) |
| 6 | Көлөмдүн астындаtage коргоо иш-аракет убактысы | 0.2S | 0.1-10с (0.2сек.) |
| 7 | Ашыкча ток коргоо мааниси | >In 80A | 1-80A (80A) |
| 8 | Over-current protection action time | 5S | 1-512с (5сек.) |
| 9 | 3 этап amp unbalance protection value | >In % | 5%-90%-OFF (25%). Not active if current < 2A. |
| 10 | 3 этап amp unbalance protection action time | 1.0 С | 0.1-10с (1сек.) |
| 11 | Фаза ырааттуулугун коргоо | ON ABC | ON or OFF (ON) |
| 12 | Күйгүзүүнүн кечигүү убактысы | 2 С | 2-255с (2сек.) |
| 13 | Fault recovery delay time | 60 С | 2-512с (60сек.) |
| 14 | Fault inquiry code | E0 | Press ▲ to view last 5 fault records (E1-E5). >U for overvoltage, <U for undervoltage. |
| 15 | Аяктоо | END | Press SET to save and exit. |
6.2 Заводдук абалга кайтаруу
To reset the device to factory settings, press and hold the ▲ жана ▼ баскычтарын бир эле учурда 3 секунд басып.
7. Операция
Once installed and configured, the device will continuously monitor the three-phase power supply. The LCD screen will automatically rotate to display the real-time voltage and current for each phase (L1, L2, L3).
Ашыкча том болгон учурдаtage, томдун астындаtage, or over-current event, the protector will automatically trip and cut off the power supply to protect connected equipment. After the fault condition clears and the recovery delay time has passed, the device will automatically restore power.
8. Кыйынчылыктарды
8.1 Fault Inquiry
If a fault occurs, the device will display an error code (E0). You can press the ▲ button to query the last 5 fault records (E1-E5). The display will indicate:
- ">U" for overvoltagэ окуялар.
- "<U" for undervoltagэ окуялар.
8.2 Phase Sequence Error
If the LCD displays "ABC" character, it indicates a phase sequence error. To correct this, arbitrarily reverse any two of the three phase lines (L1, L2, L3) at the input.
9. Техникалык тейлөө
- Аппаратты чаңдан жана нымдан таза, таза кармаңыз.
- Regularly check wiring connections for tightness and signs of wear or damage.
- Do not attempt to repair the device yourself. Refer to qualified personnel for service.
10. Кепилдик жана колдоо
For technical support, inquiries, or warranty claims, please contact the distributor:
бөлүштүрүүчү компаниялар: XNY INTERNATIONAL LIMITED
Дарек: Room 20A, Kiu Fu Commercial Building, 300 Lockhart Road, Wanchai, Hong Kong.
Тел: 0086 57761733853
Факс: 0086 577 89736991
WhatsApp: 0086 1565857 3377
Wechat: sinotimer
Skype: sinotimer
Web: www.sinotimer.com
Электрондук почта: info@sinotimer.com