1. Продукт бүтүп калдыview
The ACI A/MSCS is a miniature 'Go/No Go' current status switch designed to monitor AC current flow. It functions as a normally open (N/O) solid-state switch, activating when the sensed AC current exceeds a fixed trip point. This device is ideal for applications requiring current status indication without external power, as it induces power directly from the monitored conductor. Its split-core design facilitates easy retrofit installations.
2. Негизги өзгөчөлүктөрү
- Miniature 'Go/No Go' current status switch.
- Replaces relays in many applications due to its reliable solid-state output.
- Normally Open (N/O) solid-state switch output, non-polarity sensitive.
- Split-core design for easy installation in existing systems.
- Self-powered by the monitored conductor, requiring no external power supply.
- Fixed trip point: Activates when current exceeds 0.55 Amps.
3. Техникалык шарттар
| Атрибут | Нарк |
|---|---|
| Модел | A/MSCS |
| Иштөө режими | ON-NONE-OFF |
| Current Rating (Trip Point) | 0.55 Amps (Trip ON = Above 0.55A) |
| Сезим диапазону | 0.55-150A |
| Чыгуу | 0.5A @ 36.0 VAC/VDC |
| Байланыш түрү | Адатта ачык (N/O) |
| Туташтыргыч түрү | Crimp |
| Терминал | Бурама |
| Circuit Type | 1-жол |
| Монтаж түрү | Панел орнотуу |
| Актуатор түрү | No Actuator |
| Байланыш материалы | Жез |
| Элемент Салмагы | 0.01 унция |
4. Коопсуздук маалыматы
- ЭСКЕРТҮҮ: Орнотуу жана тейлөө квалификациялуу кызматкерлер тарабынан гана аткарылышы керек.
- Ensure power is disconnected before installation or maintenance to prevent electrical shock.
- This device is designed for use with copper conductors only. Do not use with other conductor materials.
- Observe all local and national electrical codes during installation.
- Do not exceed the specified current sense range (0.55-150A) or output ratings (0.5A @ 36.0 VAC/VDC).
5. Орнотуу жана орнотуу
The ACI A/MSCS features a split-core design for easy installation around an existing conductor. It is designed for panel mounting.
- Электр энергиясын өчүрүү: Before beginning installation, ensure that the power to the circuit being monitored is completely disconnected at the main breaker or switch. Verify with a voltage сыноочу.
- Монтаждоо: Secure the A/MSCS switch to a panel using appropriate fasteners through the mounting holes provided on the base. Ensure a stable and secure mounting location.
- Conductor Placement: Open the split-core mechanism of the A/MSCS. Carefully place the single AC copper conductor (the one you wish to monitor) through the opening in the sensor. Ensure the conductor is properly seated within the core.
- Чыгуу зымдары: Connect the output terminals of the A/MSCS to your control system, indicator light, or relay input. The output is a Normally Open (N/O) solid-state switch and is non-polarity sensitive. Use crimp connectors for secure connections to the screw terminals.
- Кайра туташтыруу: Once all connections are secure and verified, restore power to the monitored circuit.

1-сүрөт: ACI A/MSCS Fixed Trip Current Switch. This image shows the red split-core current switch with its black top housing. The top housing displays the ACI logo, model A/MSCS, manufacturer information, and electrical specifications including "Output: 0.5A @ 36.0 VAC/VDC", "Sense Range: 0.55-150A", and "TRIP ON = Above 0.55A". It also indicates "Use Copper Conductors Only" and features CE, CULUS LISTED 3SRO markings. The split-core design allows for easy placement around a conductor.
6. Иштөө нускамалары
The ACI A/MSCS operates as a simple 'Go/No Go' indicator for AC current. It requires no external power source, drawing its operating power from the magnetic field generated by the AC current flowing through the monitored conductor.
- Учурдагы мониторинг: Once installed, the switch continuously monitors the AC current in the conductor passing through its core.
- Trip Point Activation: When the AC current in the conductor exceeds the fixed trip point of 0.55 Amps, the internal solid-state switch will close. This indicates that the monitored load is "ON" or drawing sufficient current.
- Өчүрүү: If the current in the conductor falls below the trip point (e.g., the load turns "OFF" or current drops to 0A), the solid-state switch will open. This indicates that the monitored load is "OFF" or drawing insufficient current.
- Чыгуу сигналы: The closed or open state of the solid-state switch provides a signal to your connected control system, allowing for status indication or control actions.
7. Техникалык тейлөө
The ACI A/MSCS is designed for long-term, maintenance-free operation. No routine maintenance is required. Periodically inspect the wiring connections for tightness and ensure the sensor is free from physical damage or excessive dust accumulation. Always disconnect power before any inspection or cleaning.
8. Кыйынчылыктарды
- Чыгуу сигналы жок:
- Verify that power is supplied to the monitored conductor.
- Check if the AC current in the conductor exceeds the 0.55 Amp trip point. Use an appropriate current meter if necessary.
- Ensure the conductor is correctly placed within the split-core sensor.
- Inspect output wiring for proper connection and continuity.
- Incorrect Status Indication:
- Confirm that the monitored current is AC, as the sensor is designed for AC only.
- Ensure the current level is consistently above or below the 0.55 Amp trip point as expected for the desired status.
- Verify that the connected control system or indicator is functioning correctly.
- Физикалык зыян: If the unit shows signs of physical damage, replace it immediately. Do not attempt to repair damaged electrical components.
9. Өндүрүүчү колдоо
For technical assistance or further information regarding the ACI A/MSCS Fixed Trip Current Switch, please contact ACI (Automation Components, Inc.) directly.
Webсайт: www.workaci.com





