Watts LF009M3-QT

Watts 3/4" Reduced Pressure Zone Backflow Preventer (Model LF009M3-QT) Instruction Manual

Орнотуу, иштетүү жана тейлөө боюнча комплекстүү колдонмо.

1. Продукт бүтүп калдыview

The Watts 3/4 inch Lead Free Reduced Pressure Zone (RPZ) Assembly is engineered to safeguard potable water supplies from contamination due to backsiphonage or backpressure. This device complies with national plumbing codes and water authority requirements, making it suitable for continuous pressure piping applications and cross-connections identified as health hazards.

Watts 3/4 inch Reduced Pressure Zone Backflow Preventer

Image 1.1: The Watts 3/4 inch Reduced Pressure Zone Backflow Preventer assembly.

Watts backflow preventer with text 'Protect Potable Water Supplies'

Image 1.2: Visual representation emphasizing the backflow preventer's role in protecting potable water supplies.

Негизги өзгөчөлүктөрү:

2. Коопсуздук маалыматы

Always adhere to local plumbing codes and regulations during installation and maintenance. This device must be installed by a qualified professional. Failure to follow instructions may result in property damage or injury.

Diagram showing backflow preventer installation warning

Image 2.1: Important note regarding installation of backflow preventers in pits. Always consult local codes.

3. Орнотуу боюнча нускамалар

Proper installation is crucial for the effective operation of the backflow preventer. This device should be installed in a location that allows for easy access for testing and maintenance.

3.1 Орнотууга чейинки текшерүүлөр

  1. Verify that the assembly size (3/4 inch) matches the pipe size.
  2. Ташуу учурунда болушу мүмкүн болгон кандайдыр бир көрүнүктүү бузулууларды түзмөктө текшериңиз.
  3. Ensure all necessary tools and materials are available, including pipe sealant or thread tape.

3.2 Орнотуу кадамдары

  1. Түтүктөрдү даярдоо: Ensure the piping is clean and free of debris. The assembly must be installed horizontally, with the relief valve pointing downwards.
  2. Orient the Valve: Observe the flow arrow cast into the valve body to ensure correct orientation with the direction of water flow.
  3. Close-up of the Watts backflow preventer body showing flow arrow

    Сүрөт 3.1: Жакын пландан view of the valve body, highlighting the flow direction arrow for proper installation.

  4. Connect to Piping: Apply appropriate pipe sealant or thread tape to the NPT connections. Carefully thread the assembly onto the pipes, ensuring a tight, leak-free seal. Avoid overtightening.
  5. Hands installing the Watts backflow preventer onto plumbing pipes

    Image 3.2: A technician connecting the backflow preventer to the plumbing system.

  6. Support the Assembly: Provide adequate support for the assembly to prevent stress on the piping connections.
  7. Open Shutoff Valves: Slowly open the inlet and outlet shutoff valves to allow water to fill the assembly. Bleed any trapped air from the system.
  8. Агышууларды текшерүү: After installation and pressurization, thoroughly inspect all connections for leaks.
Watts backflow preventer installed in a plumbing system

Image 3.3: The Watts backflow preventer fully installed within a plumbing system, ready for operation.

4. Иштөө нускамалары

The Watts Reduced Pressure Zone Assembly operates automatically to prevent backflow. No manual intervention is required during normal operation.

4.1 Нормалдуу иштөө

4.2 Shutoff Valves

The integrated quarter-turn ball valve shutoffs are for isolating the unit for maintenance or testing. Ensure they are fully open during normal operation to allow unrestricted flow.

5. Техникалык тейлөө

Regular maintenance and testing are essential to ensure the continued proper function of the backflow preventer. Local codes typically require annual testing by a certified backflow prevention device tester.

5.1 Routine Testing

5.2 Internal Component Access

The single access cover and modular check construction allow for easy inspection and replacement of internal components if necessary.

  1. Isolate the unit by closing both inlet and outlet shutoff valves.
  2. Depressurize the assembly by opening the test cocks.
  3. Remove the bolts securing the access cover.
  4. Carefully lift the cover to access the check valve assemblies and relief valve.
  5. Ички view of the Watts backflow preventer with cover removed

    Сүрөт 5.1: View of the internal components after removing the access cover, showing the check valve assemblies.

  6. Inspect components for wear, damage, or debris. Replace any worn or damaged parts with genuine Watts replacement parts.
  7. Reassemble in reverse order, ensuring proper seating of all components and tightening bolts evenly.
  8. Slowly repressurize the system and check for leaks.

6. Кыйынчылыктарды

This section addresses common issues that may arise with the backflow preventer. For complex problems, contact a certified professional.

КөйгөйМүмкүн себепЧечим
Water leaking from relief valve
  • Fouled or damaged first check valve.
  • Fouled or damaged second check valve.
  • Debris in relief valve seat.
  • Low inlet pressure.
  • Clean or replace first check valve components.
  • Clean or replace second check valve components.
  • Clean relief valve seat.
  • Verify adequate system pressure.
Суу агымынын азайышы
  • Partially closed shutoff valves.
  • Debris lodged in the assembly.
  • Damaged check valve components.
  • Ensure shutoff valves are fully open.
  • Isolate and inspect the assembly for obstructions.
  • Inspect and replace damaged check valve components.
External leaks from body or connections
  • Improperly tightened connections.
  • Damaged O-rings or gaskets.
  • Cracked body (rare).
  • Байланыштарды бекемдеңиз (ашыкча чыңалбаңыз).
  • О-шакектерди же прокладкаларды алмаштырыңыз.
  • Contact Watts support for body damage.

7. Техникалык шарттар

АтрибутНарк
Модель номериLF009M3-QT
Өлчөмү3/4 дюйм
МатериалLead-Free Bronze
Inlet Connection Size0.75 дюйм
Inlet Connection түрүNational Pipe Tapered (NPT)
Розетка туташуу өлчөмү3/4 дюйм
Розетка туташуу түрүNPT
Максималдуу иштөө басымы175 PSI (бир чарчы дюйм үчүн фунт)
Порттардын саны3
Өлчөмдөрү (L x W x Y)Болжол менен 4 x 4 x 6 дюйм
Элемент Салмагы5.48 фунт
UPC098268705553

8. Кепилдик маалыматы

Watts products are manufactured to high standards and are typically covered by a limited warranty. For specific warranty terms and conditions applicable to your Watts LF009M3-QT Reduced Pressure Zone Assembly, please refer to the warranty documentation included with your product or visit the official Watts website. Warranty claims usually require proof of purchase and adherence to installation and maintenance guidelines.

9. Кардарларды колдоо кызматы

For technical assistance, replacement parts, or further information regarding your Watts 3/4" Reduced Pressure Zone Backflow Preventer, please contact Watts customer support.

Тектеш документтер - LF009M3-QT

Preview Watts Series LF909 Reduced Pressure Zone Assemblies - Technical Specification
Detailed technical specifications for Watts Series LF909 Reduced Pressure Zone Assemblies, including features, operation, dimensions, weights, and capacity. Designed for potable water cross-connection control.
Preview Уоттс LF909 сериясы кыскартылган басым зонасы монтаждоо инженердик спецификациясы
Watts LF909 сериясы кыскартылган басым зонасынын жыйындысы үчүн комплекстүү инженердик спецификация (21⁄2" - 10"). Интегралдык сел сенсору бар бул Lead Free кайра агымынын алдын алуучу аппараттын өзгөчөлүктөрү, иштеши, материалдары, өлчөмдөрү жана кубаттуулугу.
Preview Watts Series LF919 Reduced Pressure Zone Assembly: Installation, Maintenance, and Repair Manual
Comprehensive guide for installing, maintaining, and repairing the Watts Series LF919 Reduced Pressure Zone Assembly (1/2" - 2"). Includes safety warnings, installation procedures, servicing instructions, and troubleshooting.
Preview Watts дат баспас болоттон жасалган кош текшерүү клапаны GBS комплекти (007-SS-GBS) - Техникалык маалыматтар
Watts 007-SS-GBS дат баспас болоттон жасалган тиштүү көпөлөк клапаны жана чыпкасы бар кош текшерүү клапанынын техникалык мүнөздөмөлөрү, продукт коддору, өлчөмдөрү жана функциялары. Орто жана төмөнкү коркунучтагы орнотууларда тескери агымды алдын алуу үчүн иштелип чыккан.
Preview Watts Series 009, LF009, LFU009, SS009, U009: Installation, Maintenance, and Repair Manual
This comprehensive manual from Watts provides essential guidance for the installation, maintenance, and repair of the Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies. It details safety warnings, installation procedures, inspection, servicing, troubleshooting, and warranty information for these critical backflow prevention devices.
Preview Watts Series LF909 Reduced Pressure Zone Assemblies: Installation, Maintenance, and Repair Manual
Comprehensive guide for Watts Series LF909 Reduced Pressure Zone Assemblies, covering installation, maintenance, testing procedures, troubleshooting, and servicing. Essential for ensuring proper function and longevity.