The Eltako TLZ12-8PLUS is a compact REG staircase light timer designed for efficient control of lighting in stairwells and other areas. This electronic timer features a switch-off warning function and is suitable for mounting on a DIN rail. It offers precise time setting and supports various lamp types, including incandescent, ESL, and LED lamps.
Негизги өзгөчөлүктөр төмөнкүлөрдү камтыйт:
- Electronic function with switch-off warning.
- DIN rail mounting (EN 60715 TH35).
- Compact 1-module width (18 mm) and 58 mm installation depth.
- 1 NO contact, not potential-free, rated 16 A/250 V AC.
- Supports incandescent lamps up to 2300 W, ESL and LED lampс 200 Вт чейин.
- Control томtage 230 V and/or 8-230 V UC.
- Low standby loss of only 0.7 Watt.
- ESL optimization and multifunctionality.
- Silent operation due to bistable relay, no coil power loss or heating.
- Automatic detection of circuit type (3-wire or 4-wire).
- Precise time setting from 1 to 30 minutes with a minute scale.
2. Коопсуздук эскертүүлөрү
WARNING: This device must be installed only by qualified professionals. Improper installation can lead to electric shock, fire, or damage to the device.
- Always disconnect power at the main circuit breaker before installation, maintenance, or troubleshooting.
- Бардык зымдар жергиликтүү жана улуттук электр эрежелерине ылайык келээрин текшериңиз.
- Көрсөтүлгөн көлөмдөн ашпаңызtage жана түзмөктүн учурдагы рейтингдери.
- Аспапты нымдуулуктан жана өзгөчө температурадан сактаңыз.
3. Орнотуу жана орнотуу
The Eltako TLZ12-8PLUS is designed for modular installation on a DIN-EN 60715 TH35 mounting rail. Its compact size (1 module unit, 18 mm wide, 58 mm deep) allows for easy integration into standard electrical distribution boards.
3.1 Электр байланыш схемалары
The timer supports both 3-wire and 4-wire circuits. The device automatically detects the circuit type. Double terminals are provided for push-button and lamp connections, allowing flexibility in wiring from either top and bottom or only bottom.

This image provides technical details and wiring diagrams for the Eltako TLZ12-8PLUS timer. It includes a smaller view of the timer module, followed by connection examples for 3-wire and 4-wire circuits. The diagrams illustrate how to connect the timer for staircase lighting applications, showing connections for phase (L), neutral (N), and the switched load. Detailed German text describes functions such as electronic operation with switch-off warning, DIN rail mounting, contact type, and specific features like permanent light and button-controlled permanent light.
3.2 Connection Terminals
Refer to the product image for terminal identification:

This image displays the Eltako TLZ12-8PLUS staircase light timer. It is a compact blue module designed for DIN rail mounting. Visible features include connection terminals labeled +C1, -C2, L, N, and 3, 4, along with adjustment dials for time settings and function selection. The model name 'TLZ12-8plus' and electrical ratings '230V~/C1-C2 8-230V~' are clearly marked.
- L: Phase input (230V AC)
- N: Нейтралдуу киргизүү
- +C1 / -C2: Control томtage input (8-230V UC)
- 3/4: Switched output for the load (e.g., light fixture)
3.3 Орнотуу кадамдары
- Негизги автоматтык өчүргүчтө электр кубаты өчүрүлгөнүн текшериңиз.
- Mount the TLZ12-8PLUS onto the DIN rail in your electrical distribution board.
- Connect the phase (L) and neutral (N) wires to the corresponding terminals.
- Connect the push-button(s) to the control voltage input (+C1 / -C2) as per the wiring diagram for your specific setup (3-wire or 4-wire).
- Connect the load (e.g., staircase light) to the switched output terminals (3 / 4).
- Double-check all connections for security and correctness.
- Restore power. After installation, wait for a short automatic synchronization before the switched load is connected to the mains.
4. Иштөө нускамалары
The TLZ12-8PLUS offers various functions controlled by its rotary switches.
4.1 Убакытты орнотуу
Use the central rotary dial to set the desired lighting duration. The precise time setting ranges from 1 to 30 minutes, indicated by a minute scale.
4.2 Функцияны тандоо
The larger rotary switch allows selection of different operating modes:
- Standard Timer Function (TLZ): The lighting switches off automatically after the set time. If a power failure occurs during the timing, the lighting will switch on again once power is restored if the timer had not yet expired.
- Switch-off Warning: When activated, the lighting will flicker approximately 30 seconds before the set time expires. This flickering occurs 3 times at decreasing intervals, signaling that the light is about to turn off.
- Push-button Permanent Light: This function allows the light to be switched on permanently by pressing the push-button for longer than 1 second. The permanent light automatically switches off after 60 minutes or can be manually switched off by pressing the button for longer than 2 seconds.
- ESL Optimization: If energy-saving lamps (ESL) are used, set the switch-off warning and push-button permanent light functions to the right ESL side of the rotary switch for optimal performance.
If both push-button permanent light and switch-off warning are activated, the switch-off warning will occur after the permanent light is switched off.
5. Техникалык тейлөө
The Eltako TLZ12-8PLUS is a maintenance-free device. No user-serviceable parts are inside. For cleaning, ensure the power is disconnected and wipe the exterior with a dry, soft cloth. Do not use abrasive cleaners or solvents.
6. Кыйынчылыктарды
- Жарык күйбөйт: Check power supply, wiring connections, and the functionality of the push-button and lamp. Ensure the timer is correctly set.
- Light stays on permanently: Check if the permanent light function is accidentally activated. Verify wiring for any short circuits or incorrect connections.
- Timer does not switch off: Ensure the time setting is correct. If using ESL lamps, verify the ESL optimization setting.
- Flickering or erratic behavior: Ensure the correct lamp type is used and that the timer's capacity is not exceeded. For ESL/LED lamps, ensure the ESL optimization is correctly set.
Бул пункттарды текшергенден кийин көйгөйлөр чечилбесе, квалификациялуу электрикке кайрылыңыз.
7. Техникалык шарттар
| Атрибут | Нарк |
|---|---|
| Бренд | Eltako |
| Модель номери | TLZ12-8PLUS |
| Функция | Electronic with switch-off warning |
| Монтаж түрү | DIN rail (EN 60715 TH35) |
| Width in Division Units | 1 (18 мм) |
| Орнотуу тереңдиги | 58 мм |
| Байланыштардын саны | 1 ЖОК (Адатта ачык) |
| Rated Voltage | 250 В AC |
| Control Voltage | 230 V and/or 8-230 V UC |
| Max. Incandescent Lamp Жүктөө | 2300 Вт |
| Max. ESL/LED Lamp Жүктөө | 200 Вт |
| Күтүү режиминдеги жоготуу | 0.7 Ватт |
| Убакытты орнотуу диапазону | 1-30 мүнөт |
| Glow Lamp Учурдагы | 50 мА чейин |
| Материал | Пластик |
| Түс | Көк |
| Элемент Салмагы | 80 г |
8. Кепилдик жана колдоо
Eltako products are manufactured to high-quality standards. This product typically comes with a manufacturer's warranty. Please refer to your purchase documentation or the official Eltako webАймагыңызга тиешелүү кепилдик шарттары жана шарттары үчүн сайт.