1. Киришүү
This manual provides essential information for the safe and effective installation, operation, and maintenance of the Schneider Electric Acti9 iDD40T Residual Current Circuit Breaker (RCBO). The Acti9 iDD40T is designed to protect against electrical shock by detecting earth leakage currents and disconnecting the circuit. Please read this manual thoroughly before installation and use.
2. Коопсуздук маалыматы
ЭСКЕРТҮҮ: Electrical installation and maintenance should only be performed by qualified and authorized personnel. Failure to follow these instructions can result in serious injury or death.
- Always disconnect power at the main supply before working on electrical circuits.
- Бардык жергиликтүү жана улуттук электр кодекстеринин жана эрежелеринин сакталышын камсыз кылыңыз.
- Эгер аппарат бузулуп калса, аны колдонбоңуз.
- The test button is for functional verification only and does not replace regular electrical safety checks.
3. Орнотуу жана орнотуу
The Acti9 iDD40T RCBO is designed for DIN rail mounting. Ensure adequate space for ventilation and wiring.
3.1. Монтаждоо
- Ensure the DIN rail is securely installed within the electrical enclosure.
- Hook the top clip of the RCBO onto the DIN rail.
- Press down firmly on the bottom of the RCBO until it clicks into place on the rail.
3.2. Зымдарды туташтыруу
Refer to the diagram below for correct wiring. Ensure all connections are tight to prevent overheating and arcing.

Figure 1: Schneider Electric Acti9 iDD40T RCBO. This image shows the front view of the circuit breaker, highlighting the input and output terminals, the operating handle, and the 'Regular test' button. The 'N' terminal for neutral connection is visible at both the top and bottom.
- Connect the incoming phase (live) conductor to the top left terminal (marked 'L' or similar, typically not explicitly marked on this model but implied by standard wiring).
- Connect the incoming neutral conductor to the top right terminal (marked 'N').
- Connect the outgoing phase (live) conductor to the bottom left terminal.
- Connect the outgoing neutral conductor to the bottom right terminal (marked 'N').
- Ensure wire stripping length is appropriate for the terminals (e.g., 14mm as indicated on the device).
- Tighten terminal screws to the recommended torque (typically 2Nm, refer to device markings or manufacturer specifications).
4. Иштөө нускамалары
4.1. Күйгүзүү/өчүрүү
- Күйгүзүү: Push the operating handle upwards to the 'ON' position.
- Өчүрүү: Push the operating handle downwards to the 'OFF' position.
- Катуу абалы: If the RCBO trips due to an overload, short circuit, or earth leakage, the handle will move to an intermediate position. To reset, first push the handle fully down to 'OFF', then push it up to 'ON'.
4.2. Test Button Function
The 'Regular test' button (marked 'T' or with a test symbol) is used to verify the proper functioning of the earth leakage detection mechanism.
- Ensure the RCBO is in the 'ON' position and the circuit is live.
- Press and hold the 'Regular test' button. The RCBO should immediately trip to the 'OFF' position.
- Баскычты бошотуңуз.
- Reset the RCBO by pushing the handle fully down to 'OFF', then up to 'ON'.
- If the RCBO does not trip when the test button is pressed, it may be faulty and should be replaced immediately.
5. Техникалык тейлөө
The Acti9 iDD40T RCBO requires minimal maintenance. Regular testing is the primary maintenance activity.
- Кадимки тестирлөө: It is recommended to press the 'Regular test' button at least once every month to ensure the earth leakage protection function is operational.
- Тазалоо: If necessary, gently wipe the exterior of the device with a dry, soft cloth. Do not use abrasive cleaners or solvents. Ensure power is disconnected before cleaning.
- Текшерүү: Periodically inspect the device for any signs of physical damage, discoloration, or loose connections. Address any issues promptly.
6. Кыйынчылыктарды
If you encounter issues with your Acti9 iDD40T RCBO, refer to the following common troubleshooting steps:
| Көйгөй | Мүмкүн себеп | Чечим |
|---|---|---|
| RCBO trips immediately after being reset. | Persistent earth leakage fault, short circuit, or overload in the protected circuit. | Disconnect all loads from the circuit. Reset the RCBO. If it holds, reconnect loads one by one to identify the faulty appliance or wiring. If it still trips with no loads, consult a qualified electrician. |
| RCBO does not trip when the 'Regular test' button is pressed. | Faulty RCBO internal mechanism. | The device is faulty and must be replaced by a qualified electrician. Do not attempt to repair. |
| RCBO trips intermittently. | Intermittent earth leakage, transient overloads, or sensitive equipment causing nuisance tripping. | Check for loose connections. Monitor appliances for intermittent faults. Consider if the circuit is overloaded. Consult a qualified electrician for further diagnosis. |
7. Техникалык шарттар
Technical specifications for the Schneider Electric Acti9 iDD40T RCBO (Model A9DA2616):
| Өзгөчөлүк | Деталь |
|---|---|
| Модель номери | A9DA2616 |
| Type | Residual Current Circuit Breaker with Overcurrent Protection (RCBO) |
| поляктар | 1P+N (1 Pole + Neutral) |
| Номиналдуу ток (In) | 16 А |
| Чабуулдун ийри сызыгы | C |
| Номиналдык калдык иштөө тогу (IΔn) | 30 мА |
| Residual Current Type | AC түрү |
| Rated Short-Circuit Breaking Capacity (Icn) | 4500A/6kA (according to IEC 601009-2-1 and IEC 60947-2) |
| Rated Voltage (Ue) | 230-240 В, 50 Гц |
| Монтаж түрү | Темир менен |
| Туурасы | 8 steps of 9mm (72mm total width) |
| Өлчөмдөрү (L x W x Y) | 7.3 x 3.6 x 8.5 см |
| Салмагы | 210 грамм |
| Стандарттар | IEC 601009-2-1, IEC 60947-2 |
8. Кепилдик жана колдоо
Кепилдик маалыматы жана техникалык колдоо үчүн расмий Schneider Electricке кайрылыңыз website or contact your local Schneider Electric representative. Keep your purchase receipt as proof of purchase.
Онлайн ресурстар: www.se.com