1. Киришүү жана Продукт бүттүview
This manual provides essential information for the safe and effective installation, operation, and maintenance of the ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP Air Circuit Breaker. Please read this manual thoroughly before any operation.
The ABB SACE EMAX2 E2.2H 1600 is a fixed three-pole air circuit breaker equipped with rear horizontal terminals and a solid-state release in AC EKIP/DIP-LI R 1600. It includes four auxiliary contacts and a circuit breaker in the open-closed position.
Негизги өзгөчөлүктөрү:
- Mounting type: Plug-In Mount
- Тtage: 600.0 volts of alternating current
- Circuit breaker type: Standard
- Учурдагы рейтинг: 1600.0 amps
- Поляктардын саны: 3

Сүрөт 1: Алдыңкы view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing the Ekip Touch display, operating buttons (OPEN, Push OFF, Push ON), and the reset mechanism.
2. Орнотуу жана орнотуу
The ABB SACE EMAX2 E2.2 H 1600 is designed for plug-in mounting. Proper installation by qualified personnel is crucial for safety and optimal performance.
2.1 Таңгактан чыгаруу жана текшерүү
Carefully unpack the circuit breaker and all accessories. Inspect for any signs of shipping damage. Ensure all components listed in the packing slip are present.

Figure 2: The circuit breaker securely packed within its wooden shipping crate, indicating careful handling during transport.

Figure 3: Various accessories, such as mounting brackets and additional components, packaged separately for the circuit breaker.
2.2 Монтаждоо
This unit features a plug-in mount design. Refer to the detailed installation diagrams and instructions provided with the product for specific mounting procedures. Ensure the mounting surface is stable and capable of supporting the unit's weight (approximately 105.82 pounds).
2.3 Электр байланыштары
Connect the main power lines to the designated terminals. The unit is a three-pole breaker. Ensure all connections are secure and comply with local electrical codes and standards.

4-сүрөт: Жогорку view illustrating the three main connection points for electrical wiring, designed for robust and secure connections.
Warning: All electrical work must be performed by a qualified electrician. Disconnect all power before installation or maintenance.
3. Иштөө нускамалары
The ABB SACE EMAX2 E2.2 H 1600 features an Ekip Touch interface and mechanical push buttons for operation.
3.1 Негизги операция
- To Close (Turn On): Press the "Push ON" button (green). The breaker will close, allowing current flow.
- To Open (Turn Off): Press the "Push OFF" button (red). The breaker will open, interrupting current flow.
- Шашылыш ачык: Use the "OPEN" lever for immediate manual opening.
- Кайтаруу: After a trip event, identify and resolve the cause. Then, press the "Reset" button to reset the tripping mechanism before attempting to close the breaker again.

5-сүрөт: Детальдуу view of the operational controls, including the Ekip Touch display and the mechanical buttons for opening, closing, and resetting the breaker.
3.2 Ekip Touch Interface
The Ekip Touch display provides real-time data, settings, and diagnostic information. Refer to the separate Ekip Touch user guide for detailed navigation and configuration instructions.
4. Техникалык тейлөө
Regular maintenance ensures the longevity and reliable operation of your ABB SACE EMAX2 circuit breaker. Always disconnect power before performing any maintenance.
4.1 Күнүмдүк текшерүүлөр
- Visually inspect the breaker for any signs of damage, loose connections, or excessive dust accumulation.
- Желдетүү тешиктери ачык жана тоскоолдуксуз экенине ынаныңыз.
- Check the integrity of all wiring and terminal connections.
4.2 Тазалоо
Use a dry, lint-free cloth to clean the exterior surfaces. Do not use abrasive cleaners or solvents. For internal cleaning, consult a qualified service technician.

6-сүрөт: Каптал view revealing the intricate mechanical components and gear assembly responsible for the breaker's operation, highlighting areas that may require professional inspection.
4.3 Кесиптик тейлөө
Periodic professional servicing by ABB-certified technicians is recommended to ensure optimal performance and compliance with safety standards. This includes checking internal mechanisms and calibration of the Ekip Touch unit.
5. Кыйынчылыктарды
This section provides general guidance for common issues. For complex problems, contact ABB technical support or a qualified electrician.
5.1 Breaker Trips Frequently
- Ашыкча жүктөө: Check the connected load. Reduce the load if it exceeds the breaker's rated current (1600 A).
- Кыска туташуу: Inspect wiring for short circuits. This requires immediate attention and professional diagnosis.
- Негизги ката: If applicable, check for ground faults in the system.
- Бузулган жабдуулар: Disconnect individual equipment to identify a faulty device causing the trip.
5.2 Breaker Does Not Close
- Катуу абалы: Ensure the breaker is fully reset after a trip. The "DISCHARGED SPRING" indicator might be visible if not reset.
- Кубат жок: Verify incoming power supply.
- Механикалык тоскоолдуктар: Check for any physical obstructions preventing the mechanism from closing.

Figure 7: Product label providing critical specifications such as model number (SACE E2.2H-A), serial number, rated maximum voltage, rated short-circuit current, and UL/CSA certifications.
6. Техникалык шарттар
Detailed technical specifications for the ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP Air Circuit Breaker:
| Спецификация | Нарк |
|---|---|
| Product Main Type | SACE Emax 2 |
| Модель номери | SACE E2.2H-A |
| Номиналдуу ток (In) | 1600 А |
| Поляктардын саны | 3 |
| Учурдагы түрү | AC |
| Rated Voltage (Ur) | 690 V |
| Rated Operational Voltage | 690 В AC |
| Rated Insulation Voltage (Ui) | AC 1000 В |
| Rated Impulse Stend Voltage (Uimp) | 12 kV (acc. to IEC 60947-2) |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 100 kA, (415 V AC) 100 kA, (440 V AC) 100 kA, (500 V AC) 85 kA, (525 V AC) 85 kA, (690 V AC) 85 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA, (230 V AC) 100 kA, (380 V AC) 100 kA, (400 V AC) 100 kA, (415 V AC) 100 kA, (440 V AC) 100 kA, (500 V AC) 85 kA, (660 V AC) 85 kA, (690 V AC) 85 kA |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Кыска убакытка туруштук берүү агымы Төмөн Voltage (Icw) | for 1 s 85 kA, for 3 s 66 kA |
| Rated Uninterrupted Current (Iu) | 1600 А |
| Электрдик туруктуулук | Ue =<440 V 12000 cycle, Ue = 500 ... 690 V 10000 cycle (30 cycles per hour) |
| Механикалык туруктуулук | 25000 cycle (60 cycles per hour) |
| Power Loss | 288 Вт |
| Продукциянын өлчөмдөрү | 15.08 x 12.48 x 16.73 дюйм |
| Салмагы | 105.82 фунт |
| Келип чыккан өлкө | Италия |
Note: Specifications are subject to change without notice. Always refer to the product label and official ABB documentation for the most accurate and up-to-date information.

Figure 8: Product identification label, including the EAN/UPC code 8057558336022, which can be used for product verification and lookup.
7. Кепилдик жана колдоо
For warranty information and technical support, please refer to the official ABB documentation included with your product or visit the official ABB webсайт.
- Кайтаруулар: Бул продукт 30 күндүн ичинде оңой кайтарып берүүгө укуктуу. Чоо-жайын билүү үчүн чекене сатуучунун кайтаруу саясатын текшериңиз.
- Кардарларды колдоо: For assistance, contact customer support through your purchase platform or directly via ABB's official channels.
- ABB Store: You can find more information and products from ABB by visiting the official ABB Store.





