1. Киришүү
The Run Bison 32W LED Emergency Driver is designed to convert existing LED luminaires into emergency lighting fixtures. This unit provides a minimum of 90 minutes of illumination during a loss of normal AC power, ensuring safety and compliance in commercial and industrial settings. It is UL Listed, guaranteeing adherence to stringent safety and performance standards.

Image 1.1: The Run Bison 32W LED Emergency Driver, showing its compact design and flexible conduit for easy installation.
2. Негизги өзгөчөлүктөрү
- Ар тараптуу колдонуу: Suitable for LED commercial lights with input power above 10W but below 300W and with a 0-10V dimming function. Compatible with recessed lights, panel lights, surround lights, and high bay lights. Also compatible with 10W-32W LED lights without a 0-10V dimming function.
- Extended Emergency Time: Provides up to 90 minutes of illumination during AC power loss after a 24-hour charging period (36 hours for 25W and 32W models).
- Эс алуу режими: Features a rest mode, activated by pressing the test switch for more than 3 seconds in emergency mode, which minimizes leakage current and extends storage time.
- UL тастыкталган: Fully compliant with strict UL standards, ensuring trustworthy performance. Features 100-277V AC input and 150-270VDC output. Maximum input power and output power are 32W. Maximum input current is 120mA.
- Туруктуу дизайн: Rated for high ambient temperatures up to 122°F (50°C) and low start-up temperatures down to 41°F (5°C). Ensures a rated life of 50,000 hours.

Сүрөт 2.1: Бүттүview of the LED Emergency Driver's key performance specifications and features.
3. Техникалык шарттар
| Спецификация | Нарк |
|---|---|
| Бренд | Бизонду чуркап барыңыз |
| Модель номери | RBHV32W-EM-190V-1PK |
| Продукциянын өлчөмдөрү | 13.6 x 1.7 x 1.8 дюйм |
| Материал | Металл |
| Power Source | AC |
| Тtage | 190 Volts (Input: 100-277V AC) |
| Ватtage | 32 watts (Max Input/Output) |
| Орточо жашоо | 50,000 саат |
| Өзгөчө кырдаал убактысы | Over 90 Minutes |
| Сертификаттар | UL Certified |

Image 3.1: Physical dimensions and certifications of the emergency driver.
4. Пакеттин мазмуну
Пакетти ачканда, бардык компоненттер бар экенин жана бузулбаганын текшериңиз:
- LED Emergency Backup Driver (1 unit)
- Installation accessories (e.g., mounting hardware, wire nuts)
5. Орнотуу жана орнотуу
Маанилүү коопсуздук маалыматы: Installation should only be performed by a qualified electrician in accordance with the National Electrical Code (NEC) and local codes. Disconnect power at the circuit breaker before installation or servicing.
5.1 Электр өткөргүч схемасы
Refer to the diagram below for proper wiring connections. Ensure all connections are secure and insulated.

Image 5.1: Detailed wiring diagram for connecting the emergency LED driver to a lighting fixture and power source.
- AC Line (24/7) - Red: Connect to unswitched hot AC power.
- Neutral - White: Connect to AC neutral.
- AC Line Switch - Black: Connect to switched hot AC power.
- Ground - Green: Connect to electrical ground.
- Dimmer (Purple/Pink) - 22AWG: Connect to 0-10V dimming control wires of the LED fixture (if applicable).
- LED Module (Brown/Blue) - 18AWG: Connect to the LED module of the fixture.
- Orange Wires: Connect to the test switch/pilot light.
5.2 Compatible Lighting Fixtures
This emergency driver is compatible with a wide range of LED lighting fixtures. It supports 0-10V dimmable fixtures from 32W to 300W, and non-dimmable fixtures up to 31W.

Сүрөт 5.2: Мисamples of compatible lighting fixtures for the emergency driver.
6. Иштөө нускамалары
Once properly installed and connected to AC power, the emergency driver will begin charging its internal battery. The pilot light on the test switch will illuminate to indicate normal operation and charging status.
- Кадимки операция: When AC power is present, the LED fixture operates normally, and the emergency driver's battery charges.
- Өзгөчө кырдаал режими: In the event of an AC power failure, the emergency driver automatically switches the connected LED fixture to emergency mode, providing illumination for over 90 minutes.
- Сыноо которуштуруу: Press the test switch to simulate an AC power failure and verify the emergency function. The pilot light indicates the charging status (e.g., green for charged, red for charging/fault).
- Эс алуу режими: To enter rest mode, press and hold the test switch for more than 3 seconds while in emergency mode. This reduces battery discharge during extended storage.

Image 6.1: Common applications where the emergency driver can be utilized.
7. Техникалык тейлөө
Regular maintenance ensures optimal performance and longevity of your emergency driver.
- Баштапкы төлөм: Allow the unit to charge for a minimum of 24 hours (36 hours for 25W and 32W models) before the first emergency test to ensure full battery capacity.
- Ай сайын тестирлөө: Conduct a monthly 30-second test using the test switch to ensure the emergency function is operational.
- Жылдык тестирлөө: Perform an annual 90-minute discharge test. Disconnect AC power to the unit and verify that the fixture remains illuminated for the full 90 minutes.
- Тазалоо: Keep the unit clean and free from dust. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
- Батареяны алмаштыруу: The internal battery is designed for long life. If the unit fails to provide 90 minutes of emergency illumination after a full charge, the battery may need replacement. Contact qualified personnel for service.
- Жоюу: The battery inside is rechargeable and must be recycled or disposed of properly according to local regulations. Do not dispose of with general waste.
8. Кыйынчылыктарды
If you encounter issues with your emergency driver, refer to the following common problems and solutions:
| Көйгөй | Мүмкүн себеп | Чечим |
|---|---|---|
| Fixture does not illuminate in emergency mode. | No AC power to the emergency driver; Battery not charged; Faulty wiring; Defective unit. | Check circuit breaker and power supply. Allow 24-36 hours for initial charge. Verify all wiring connections. Contact support if issue persists. |
| Pilot light is off or red. | No AC power; Battery charging; Battery fault. | Ensure AC power is supplied. Allow time for charging. If red after full charge, contact support. |
| Emergency illumination time is less than 90 minutes. | Insufficient charging time; Battery nearing end of life; Incorrect load. | Ensure unit has charged for 24-36 hours. If battery is old, consider replacement. Verify connected LED load is within specifications. |
| Test switch does not activate emergency mode. | Faulty test switch; Wiring issue. | Check connections to the test switch. If switch is damaged, contact support for replacement. |
9. Кепилдик жана колдоо
The Run Bison 32W LED Emergency Driver is backed by a 5 жылдык өндүрүүчүнүн кепилдиги, кадимки колдонуу жана тейлөө учурундагы материалдардагы жана жасалгалоодогу кемчиликтерди жабуу.
For technical support, warranty claims, or further assistance, please contact Run Bison customer service through the retailer's platform or visit the official Run Bison webсайт. Колдоо кызматына кайрылганда продуктуңуздун моделинин номерин жана сатып алынган күнүн жазып коюңуз.